Plan Review Notes
Plan Review Notes For Permit 07070249
Permit Number 07070249
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2007-07-25 13:21:20***DENIED***
  
 1) THE MINIMUM SAFETY MARGIN SHALL BE NOT LESS THAN 5.0
 PSI IN ACCORDANCE WITH LOCAL REQUIREMENTS. PLEASE
 PROVIDE THIS INFORMATION WITH THE HYDRAULIC ANALYSIS.
  
 2) A DOUBLE DETECTOR CHECK ASSEMBLY WAS NOT SHOWN ON
 PLANS. PLEASE PROVIDE A DETAIL SHOWING ASSEMBLY OR
 ILLUSTRATE HOW BACKFLOW REQUIREMENTS WILL BE MET.
  
 3) CENTRAL STATION MONITORING IS REQUIRED. NEW SYSTEMS
 SUPERVISING AUTOMATIC SPRINKLER PROTECTION TO BE UL
 CERTIFIED FOR CENTRAL STATION SERVICE.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756