| Plan Review Notes For Permit 07070249 |
| Permit Number |
07070249 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-07-25 13:21:20 | ***DENIED*** | | | | | | 1) THE MINIMUM SAFETY MARGIN SHALL BE NOT LESS THAN 5.0 | | | PSI IN ACCORDANCE WITH LOCAL REQUIREMENTS. PLEASE | | | PROVIDE THIS INFORMATION WITH THE HYDRAULIC ANALYSIS. | | | | | | 2) A DOUBLE DETECTOR CHECK ASSEMBLY WAS NOT SHOWN ON | | | PLANS. PLEASE PROVIDE A DETAIL SHOWING ASSEMBLY OR | | | ILLUSTRATE HOW BACKFLOW REQUIREMENTS WILL BE MET. | | | | | | 3) CENTRAL STATION MONITORING IS REQUIRED. NEW SYSTEMS | | | SUPERVISING AUTOMATIC SPRINKLER PROTECTION TO BE UL | | | CERTIFIED FOR CENTRAL STATION SERVICE. | | | | | | | | | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL | | | FIRE PLAN REVIEW | | | FIRE PREVENTION (561) 804-4756 |
|