| 2007-07-28 10:47:15 | |
| | |
| | DENIED |
| | |
| | 1)PROVIDE WIND DESIGN DATA ON DRAWINGS PER |
| | 1603.1.4 FBC |
| | |
| | 2)WORK ON EXISTING BUILDINGS IS COVERED UNDER THE FBC |
| | (EXISTING) AS SUCH A DESIGN PROFESSIONAL OR OWNERMUST |
| | ELECT ONE OR A COMBINATION OF LEVELS OF ALTERATION PER |
| | 301.5 FBC (EXISTING) |
| | |
| | 3)PROVIDE STRUCTURAL MAKEUP OF BUILDING (WOOD FRAME, |
| | BLOCK, ETC.) FOR ATTACHMENT METHODS THAT WILL BE USED |
| | TO SECURE DOORS AND WINDOWS. |
| | |
| | 4)PROVIDE DOOR AND WINDOW OPENING DESIGN PRESSURES |
| | |
| | 5)CLARIFY THE POST IN THE SCHEDULE FOR MARKS 006 AND |
| | 007, IS THIS STRUCTURAL OR A MULLION FROM THE PRODUCT |
| | APPROVAL, IF SO GIVE SIZE |
| | |
| | 6)MAKE THE FOLLOWING CORRECTIONS TO THE PRODUCT |
| | APPROVALS: |
| | |
| | A)THE MIAMI-DADE REPORT THAT IS PART OF THE FLORIDA |
| | STATEWIDE PRODUCT APPROVAL FOR THE FIXED WINDOWS IS |
| | INCORRECT PLEASE USE THE LINK ON THE WEBSITE TO |
| | DOWNLOAD THE CORRECT REPORT THAT WAS USED TO VALIDATE |
| | THE STATE APPROVAL (06-1201.05) |
| | |
| | B)PROVIDE THE GLAZING AND ANCHOR TYPE FOR THE WINDOWS |
| | AS THESE MAKE A DIFFERENCE IN THE DESIGN PRESSURES (SEE |
| | LARGE WINDOWS 013 AND 014 SIZES IN PRODUCT APPROVAL) |
| | |
| | C)PROVIDE MULLION SIZES AND ANCHOR TYPE |
| | |
| | 7)PLEASE NOTE THE A 4X FEE WAS ASSESSED BY CHUCK |
| | JORDAN (805-6673) AND IS REQUIRED TO BE PAID PRIOR TO |
| | FURTHER PLAN REVIEW AND PERMIT ISSUANCE |
| | |
| | BLDG PLAN REVIEW |
| | ADRIAN MORSE |
| | 561-805-6716 |
| | |
| | |