| 2007-09-24 13:35:30 | |
| | |
| | |
| | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: |
| | |
| | THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004 |
| | RESIDENTIAL BUILDING |
| | CODE, 2005 NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC |
| | AS |
| | AMENDED, CHAPTER 1, AND FOUND NONCOMPLIANT WITH THE |
| | FOLLOWING: |
| | |
| | THESE COMMENTS ARE FROM THE PREVIOUS REVIEW7/17/07. |
| | |
| | 4} THERE ARE TWO PANELS SHOWN ON THE RISER DIAGRAM, |
| | ONLY ONE SHOWN IN THE GARAGE, PLEASE LOCATE ALL |
| | EQUIPMENT ON THE PLAN. *THE METER AND DISCONNECT ARE |
| | NOT SHOWN ON THIS RESUBMITTAL EITHER. 106.1.1 FBC. |
| | |
| | 8} THE DINING ROOM RECEPTACLES MUST COMPLY WITH |
| | 210.52(B)(1), NOTE FOR PANEL SCHEDULE.* THEE PANEL |
| | SCHEDULE HAS A 15 AMP BREAKER, MUST BE A 20 AMP CIRCUIT |
| | TO COMPLY. |
| | |
| | 9} THE AIR HANDLER LOCATED IN THE CLOSET IS IN |
| | VIOLATION OF 240.24(D) FOR OVERCURRENT PROTECTION. ALSO |
| | THERE IS A 120 VOLT RECEPTACLE SHOWN AS A DISCONNECT. * |
| | NOW THE ?CLOSET? IS RENAMED ?STORAGE?, SEE 422.17 TO |
| | DETERMINE IF THIS UNIT NEEDS TO BE WALLED OFF FROM |
| | ITEMS INTENDED TO BE STORED IN THIS ROOM. |
| | |
| | THESE ARE NEW COMMENTS FOR THIS REVIEW GENERATED BY THE |
| | PANEL SCHEDULE BEING ADDED TO THE PLAN. |
| | |
| | 1} SEE COMMENT #8 ABOVE. |
| | |
| | 2} THERE IS ONLY ONE SMALL APPLIANCE CIRCUIT IN THE |
| | PANEL SCHEDULE, PER 210.11(C)(1), A MINIMUM OF TWO ARE |
| | REQUIRED. |
| | |
| | 3} BATHROOM CIRCUITS ARE REQUIRED TO BE 20 AMP PER |
| | 210.11(C)(3) ONLY THE MASTER BATH IS LISTED IN THE |
| | SCHEDULE, AND IT HAS A 15 AMP BREAKER. |
| | |
| | 4} THE NOTE FOR PANEL ?A? ON THE RISER DIAGRAM READS |
| | ?MAIN METER?, CLARIFY IF THIS IS A METER MAIN |
| | COMBINATION PIECE OF SERVICE EQUIPMENT. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |