| 2007-07-17 13:53:59 | |
| | |
| | NONCOMPLIANT |
| | |
| | PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE |
| | COMPLIANCE AND RESUBMIT FOR REVIEW. |
| | |
| | 1} THE ENGINEERING FIRM LISTED ON THE TITLE BLOCK SHALL |
| | INDICATE THE CERTIFICATE OF AUTHORIZATIONNUMBER ALONG |
| | WITH OTHER INFORMATION REQUIRED BY 61G15-23.002 FLORIDA |
| | ADMINISTRATIVE CODE. |
| | |
| | 2} PROVIDE A LOAD CALCULATION FOR THE ELECTRICAL |
| | SERVICE, INDICATING ALL EXISTING LOADS AND ALL LOADS TO |
| | BE IMPOSED BY THE ADDITION OF THE NEW EQUIPMENT. 215.5 |
| | NEC 2005. SEE 220.80 2005 NEC. SEE SMALL APPLIANCE AN |
| | AHU. |
| | |
| | 3} THE 2005 NEC WAS ADOPTED BY THE FLORIDA LEGISLATURE |
| | EFFECTIVE 8 DECEMBER 2006. THE APPLICATION FOR THIS |
| | PROJECT WAS AFTER THAT DATE AND THE PLANS ARE SUBJECT |
| | TO THAT CODE. PLEASE CHANGE ALL NOTES TO REFLECT THIS |
| | CHANGE. |
| | |
| | 4} THERE ARE TWO PANELS SHOWN ON THE RISER DIAGRAM, |
| | ONLY ONE SHOWN IN THE GARAGE, PLEASE LOCATE ALL |
| | EQUIPMENT ON THE PLAN. |
| | |
| | 5} PROVIDE PANEL SCHEDULES PER 408.4, NEC,CIRCUIT |
| | DIRECTORY OR CIRCUIT IDENTIFICATION |
| | EVERY CIRCUIT AND CIRCUIT MODIFICATION SHALL BE LEGIBLY |
| | IDENTIFIED AS TO ITS CLEAR, EVIDENT, AND SPECIFIC |
| | PURPOSE OR USE. THE IDENTIFICATION SHALL INCLUDE |
| | SUFFICIENT DETAIL TO ALLOW EACH CIRCUIT TO BE |
| | DISTINGUISHED FROM ALL OTHERS. |
| | |
| | 6} THE KITCHEN PENINSULAR RECEPTACLE SPACING MUST |
| | COMPLY WITH 210.52(C)(3). |
| | |
| | 7} RECEPTACLE SPACING MUST COMPLY WITH 210.52(A)(1), |
| | SEE PROPOSED FAMILY ROOM. |
| | |
| | 8} THE DINING ROOM RECEPTACLES MUST COMPLY WITH |
| | 210.52(B)(1), NOTE FOR PANEL SCHEDULE. |
| | |
| | 9} THE AIR HANDLER LOCATED IN THE CLOSET IS IN |
| | VIOLATION OF 240.24(D) FOR OVERCURRENT PROTECTION. ALSO |
| | THERE IS A 120 VOLT RECEPTACLE SHOWN AS A DISCONNECT. |
| | |
| | NOTE: IF METAL STUDS ARE USED THEY MUST COMPLY WITH |
| | 2704.1, 2004 FBC: METAL FRAMING MEMBERS SHALL BE BONDED |
| | TO THE EQUIPMENT GROUNDING CONDUCTOR FOR THE CIRCUIT |
| | THAT MAY ENERGIZE THE FRAMING. PLEASE SEE ARTICLE.AND |
| | NOTE ON PLAN. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLANS EXAMINER |