| 2007-07-28 14:34:13 | |
| | |
| | DENIED |
| | |
| | 1)PLANS AND SPECIFICATIONS DESIGN PARAMETERS SHALL |
| | COMPLY WITH THE 2004 FLORIDA BLDG CODE WITH 2006 |
| | AMENDMENTS PER 106.1.1 FBC* |
| | |
| | 2)IN AN EXISTING BUILDING WHERE ALTERATIONS ARE BEING |
| | MADE A DESIGN PROFESSIONAL MUST ELECT THE LEVEL OF |
| | ALTERATION PER 301.5 OF EXISTING BUILDING CODE AND |
| | STATE ALONG WITH THE TYPE OF CONSTRUCTION ON THE |
| | DRAWINGS |
| | |
| | 3)THE CLAIMED VALUATION ON THE PERMIT APPLICATION IS |
| | LOW. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS |
| | AND SYSTEMS SHALL BE THE TOTAL REPLACEMENT COST |
| | EXCLUDING LAND VALUE. OUR VALUATION REFERENCE IS ICC |
| | (BVD), MARSHALL-SWIFT AND MEANS COST ANALYSIS SERVICES |
| | PER 108.3 FBC* |
| | |
| | 4)THE STATE OF FLORIDA REQUIRES COLLECTION OF A RADON |
| | SURCHARGE ON ALL NEW CONSTRUCTION COMPUTED ON UNDER |
| | ROOF FLOOR SPACE PER 10D-91 FAC. THESE FEES WILL BE |
| | ADDED TO THE PERMIT APPLICATION FEES |
| | |
| | NOTE: FEES ARE DUE IN THE AMOUNT OF $ 158.88FOR |
| | INCREASED VALUE AND STATE RADON FEES THIS AMOUNT IS |
| | REQUIRED TO BE PAID PRIOR TO FURTHER PLAN REVIEW |
| | |
| | 5)PROVIDE 2 COPIES OF A RECENT SURVEY SHOWING THE |
| | PROPOSED BUILDING/ADDITION WITH ALL SIDE AND REAR |
| | SETBACKS |
| | |
| | 6)A TITLE BLOCK WITH THE INFORMATION SPECIFIED PER |
| | 61G1-16.004 FAC SHALL BE PRESENT ON DRAWINGS ISSUED BY |
| | THE RESPONSIBLE ARCHITECT AND MUST, |
| | AT A MINIMUM CONTAIN |
| | 1) FIRM NAME,ADDRESS, AND TELEPHONE # |
| | 2) FIRM LICENSE # |
| | 3) NAME OF PROJECT |
| | 4) DATE PREPARED |
| | 5) A SPACE FOR SIGNATURE & DATED SEAL |
| | 6) A SPACE FOR PRINTED NAME OF PERSON |
| | SEALING THE DOCUMENT |
| | |
| | 7)A CERTIFICATE OF AUTHORIZATION SHALL BE REQUIRED |
| | FOR A CORPORATION, LIMITED LIABILITY COMPANY, OR |
| | PARTNERSHIP, OFFERING ARCHITECTURAL SERVICES TO THE |
| | PUBLIC JOINTLY OR SEPARATELY. |
| | PER 481.219(2) F.S. |
| | |
| | 8)IN AREAS OF QUESTIONABLE SOILS AS SHOWN IN THE |
| | OFFICIAL ZONING MAP OF THE CITY OF WEST PALM BEACH, 2 |
| | COPIES OF A SOIL TEST REPORT SHALL BE SUBMITTED PER |
| | R401.4 FBC RES. |
| | |
| | 9)THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE |
| | 9B-72 (PRODUCT APPROVALS) SHALL BE REVIEWED AND |
| | APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO |
| | SUBMITTAL FOR JURISDICTIONAL APPROVAL PER 106.3.3 FBC* |
| | (SEE ROOF TILES) |
| | |
| | 10)GENERAL CONTRACTOR CANNOT INSTALL CONCRETE TILE |
| | ROOFING UNDER THE SCOPE OF HIS LICENSE, REMOVE FROM |
| | PERMIT APPLICATION AND HAVE ROOFING CONTRACTOR APPLY |
| | FOR PERMIT |
| | |
| | 11)PROVIDE ATTIC ACCESS ON DRAWINGS TO ALL AREAS AS |
| | REQUIRED PER R807.1 FBC RES. |
| | |
| | 12)PROVIDE DETAIL (WOOD FRAME, BLOCK) ON PONY WALL AT |
| | NEW FRONT ENTRY ALCOVE WHERE EXISTING 8'-0" WALL WILL |
| | BE RAISED TO 12'-0" AND THE ATTACHMENT METHOD |
| | |
| | 13)PROVIDE MIN ROOF SHEATHING ATTACHMENT PER |
| | R803.2.3.1 FBC RES. NOTE THAT ONLY 8D OR BETTER "RING |
| | SHANK" NAIL MAY BE USED |
| | |
| | 14)TRUSS ENGINEERING HAS NO WIND DESIGN DATA ON THE |
| | SIGNED AND SEALED INDEX SHEET AND THE LAYOUT DRAWING |
| | HAS THIS INFORMATION BUT IS NOT SIGNED AND SEALED |
| | |
| | 15)PHOTO COPIED, STAMPED OR REPRODUCED SIGNATURES ARE |
| | NOT ACCEPTABLE PER 471.025 F.S. TRUSS INDEX SHEET MUST |
| | HAVE TRUE SIGNATURE |
| | |
| | 16)TRUSS DESIGN LOADS AND DESIGN LOADS ON THE |
| | DRAWINGS DO NOT MATCH (SEE DL AND LL FOR TOP CORD) MAY |
| | BE DUE TO CHANGE FROM SHINGLE ROOFING TO CONCRETE TILE |
| | |
| | 17)PROVIDE COMPLETE ANCHOR/TIE DOWN SCHEDULE THAT |
| | INCLUDES THE STATEWIDE PRODUCT APPROVAL # OR THE |
| | SIMPSON TIE INDEX SHEET WITH THE CHOSEN ANCHORS MARKED |
| | (THIS WOULD BE PREFERABLE TO PRODUCT APPROVALS FOR ALL |
| | STRAPS & TIES THAT WILL BE USED) |
| | |
| | 18)PER 106.1.3 FBC* THE BUILDING OFFICIAL MAY |
| | ESTABLISH THROUGH DEPARTMENTAL POLICY, STANDARDS FOR |
| | PLANS AND SPECIFICATIONS "NO WHITE OUT, PENCIL OR INK" |
| | ON DRAWINGS |
| | |
| | 19)PROVIDE CORRECT MIAMI-DADE NOA FOR THE SERIES |
| | FD-750 FRENCH DOORS THAT THE FLORIDA STATEWIDE PRODUCT |
| | APPROVAL USES FOR VALIDATION (07-0103.02) PRODUCT |
| | APPROVALS WERE SUBMITTED FOR SERIES FD-101 FRENCH DOORS |
| | ALSO ARE BOTH BEING USED IF SO SPECIFY WHERE EACH ARE |
| | USED ON THE DRAWING |
| | |
| | 20)PROVIDE A PRODUCT APPROVAL FOR THE FRONT ENTRY |
| | PANEL DOORS |
| | |
| | 21)A RECORDED COPY OF THE NOTICE OF |
| | COMMENCEMENT IS REQUIRED PRIOR TO |
| | A PERMIT BEING ISSUED |
| | |