| Plan Review Notes For Permit 07070220 |
| Permit Number |
07070220 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-08-23 14:59:51 | *** DENIED *** | | | | | | | | | 1) NOTE:PLEASE PROVIDE MINIMUM GROUNDING ELECTRODE | | | SYSTEM DETAIL FOR ELECTRICAL SERVICE OF STRUCTURE AS | | | REQUIRED PER 250.50 OF THE 2005 NEC/NFPA-70. | | | ** PLEASE SEE STRUCTURAL STEEL BONDING AS REQUIRED PER | | | SECTION NOTED ABOVE. | | | | | | 2) NOTE: PLEASE PROVIDE DETAIL FOR ANY AND ALL | | | UNDERGROUND CONDUITS BEING INSTALLED FOR DUCT BANKS TO | | | AND FROM FPL VAULT BEING INSTALLED. | | | PLEASE INDICATE THE SIZE OF THE CONDUITS, THE NUMBER OF | | | THE CONDUITS AND A PRELIMINARY CONDUCTOR | | | SCHEDULE/REFERENCE TO THE SIZE OF THE SERVICE BEING | | | INSTALLED. | | | THERE IS A UNDERGROUND CONDUIT DUCT BANK SHOWN ON THE | | | *S* SHEET(S) WHICH DOES NOT INDICATE IF THIS IS FPL, | | | ETC. | | | FBC 106.1.2 | | | | | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | | | | |
|