| 2007-07-31 14:11:39 | BUILDING PLAN REVIEW |
| | PERMIT: 07070220 |
| | ADD: 500 BANYAN BLVD |
| | CONT: CATALFUMO |
| | TEL: (561)307-4746 |
| | |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2006 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | REVIEW |
| | ACTION: DENIED |
| | |
| | 1)--- VERY IMPORTANT STATEMENT --- |
| | PLEASE DO NOT IGNORE! |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| | YOUR ANTICIPATED COOPERATION. |
| | |
| | 2) )OF THE UTILTY SIGN OFF WE ARE MISSING THE WATER |
| | DEPARTMENT OR UTILITIES ENGINEERING DEPARTMENT. SHEET |
| | C-9 DOES INDICATE A 14' ALLEYWAY BETWEEN LOT1 AND LOT |
| | 10, A COPY OF THE UNITY OF TITLE IS IN HAND. PLEASE |
| | UPDATE SHOWING THE ABANDOMENT OF THE ALLEYWAY AND THEN |
| | THE SIGN OFF FROM ENGINEERING AND UTILITIES. SHEET |
| | S1-1.0INDICATES THERE WILL BE AN FPL DUCTBANK BENEATH |
| | THE BUILDING EAST TO WEST PLEASE PROVIDE THE RECORDED |
| | UTILITY EASEMENT FOR THIS AREA AS WELL AS FOR THE FPL |
| | VAULT. |
| | |
| | 3) SHEETLS0.0PLEASE CORRECT THE ADDRESS TO 500 |
| | BANYAN. |
| | |
| | 4) NOTE CORRECT FOR BUILDING PLAN LS0.0 FPL VAULT 3HR |
| | WALL PLANS INDICATE 90 MINUTE DOORS PLEASE SEE TABLE |
| | 715.3 3HR WALLS/ 3 HR OPENING PROTECTIVES. |
| | |
| | 5)S1-1.0 INDICATES THE USE OF 16" AUGER PILE WHERE AS |
| | THE SOILS REPORTS DO NOT REFLECT USING SUCH A SYSTEM. |
| | PLEASE PROVIDE THE GEOENGINEERS CALCULATIONS FOR DEPTH |
| | OF PILE. |
| | |
| | 6) SOILS REPORTS SUBMITTED ARE COPIES NOT ORIGINAL |
| | SIGNED AND SEALED DOCUMENTS. NOTE THIS WILL BE A |
| | THRESHOLD BUILDING REQUIRING THREE DOCUMENTS TO BE |
| | SUBMITTED. |
| | |
| | 7) WPB AMENDMENT 105.13.6. W.P.B. CONSTRUCTION SERVICES |
| | DEPARTMENT REQUEST FOR THRESHOLD BUILDINGS A SPECIAL |
| | INSPECTOR AS REQUIRED BY S. 553.79(5) FLORIDA STATUTES |
| | TO THE MINIMUM INSPECTIONS REQUIRED BY THIS CODE. |
| | CONTACT HAROLD PISKURA MANAGER OF THE SPECIAL INSPECTOR |
| | PROGRAM AT (561) 805-6711 FOR FURTHER INFORMATION |
| | BEFORE THE PERMIT MAY BE ISSUED. |
| | |
| | 8) S2-4.0 VS DUCT BANK WHICH SYSTEM WILL BE INSTALLED |
| | FIRST,DUCT BANK, VIBROFLOTATION OR THE FOUNDATION SEE |
| | DETAIL# 8.IF THE DUCT BANK IS PLACED AFTER THE FOOTERS |
| | THE SOILS NATURAL REPOSE WILLUNDERMINE THE |
| | FOUNDATION. |
| | |
| | 9)105.13. SPECIAL FOUNDATION PERMIT.WHEN APPLICATION |
| | FOR A PERMIT TO ERECT OR ENLARGE A BUILDING HAS BEEN |
| | FILED, & PENDING ISSURANCE OF SUCH PERMIT, THE BUILDING |
| | OFFICIAL MAY, AT HIS/ HER DISCRETION, ISSUE A SPECIAL |
| | PERMIT FOR THE FOUNDATION ONLY, UPON WRITTEN REQUEST OF |
| | THE OWNER AND CONTRACTOR. THE HOLDER OF SUCH A SPECIAL |
| | PERMIT IS PROCEEDING AT HIS OR HER OWN RISK AND WITHOUT |
| | ASSURANCE THAT A PERMIT FOR THE |
| | REMAINDER OF THE WORK WILL BE GRANTED AND THAT |
| | CORRECTIONS WILL NOT BE REQUIRED IN ORDER TO MEET THE |
| | PROVISIONS OF THE TECHNICAL CODE. |
| | |
| | BUILDING PLAN REVIEW II |
| | JIM WITMER C. B. O. |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |
| | E-MAIL: [email protected] |
| | |
| | |