| 2007-08-22 14:07:02 | ****CORRECTIONS**** |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | FBC FLORIDA BUILDING CODE 2004 |
| | FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL |
| | |
| | FROM PREVIOUS LIST: |
| | |
| | |
| | _XX_3.COMPLETE THE ATTACHED INSTALLATION SCHEDULE |
| | OR PROVIDE ALL INFORMATION TO SHOW CODE COMPLIANCE IN |
| | ANOTHER FORMAT.NOTE THAT THE ANCHOR SPACING ON PAGE 2 |
| | WAS BLANK.ALSO, THE SHUTTER CONNECTION MOUNTING TYPE |
| | SHOULD CORRELATE WITH THE DETAIL MARKERS ON THE ANCHOR |
| | SCHEDULE; IN THIS CASE, A THROUGH L.IT APPEARS THAT |
| | YOU ARE USING A (12). |
| | |
| | 2ND REVIEW - YOU ARE SPECIFYING A 3" EDGE DISTANCE. |
| | YOU HAVE WRITTEN "HV 12" ON THE INSTALLATION SCHEDULE. |
| | THE ANCHOR SCHEDULE ON THE PRODUCT APPROVAL USES A |
| | THROUGH L FOR SHUTTER CONNECTION MOUNTING TYPES.YOU |
| | HAVE CIRCLED BOTH A AND H ON THE PRODUCT APPROVAL.3" |
| | EDGE DISTANCE REQUIRES A FACTOR OF .83, SEE SHEET 14 OF |
| | THE PRODUCT APPROVAL.TAPCON, 8' SPAN, 3" EDGE |
| | DISTANCE, CONNECTION H REQUIRES 8.5 X .83 SPACING, YOUR |
| | INSTALLATION SCHEDULE STATES 8". |
| | |
| | PLEASE REVISE INSTALLATION SCHEDULE. |
| | |
| | 3RD REVIEW - THE ANCHOR SPACING WAS REVISED BUT THE |
| | SHUTTER CONNECTION MOUNTING TYPE STILL STATES "HV12". |
| | THIS SHOULD CORRELATE WITH THE ANCHOR SCHEDULE, A |
| | THROUGH L.YOU'VE CIRCLED INFORMATION ON THE CHART FOR |
| | A AND H, ARE THESE THE CONNECTION TYPES YOU ARE USING? |
| | PLEASE INCLUDE THIS INFORMATION AS REQUESTED.REVISE |
| | INSTALLATION SCHEDULE. |
| | |