2007-08-15 07:52:19****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2004
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
  
 FROM PREVIOUS LIST:
  
  
 _XX_3.COMPLETE THE ATTACHED INSTALLATION SCHEDULE
 OR PROVIDE ALL INFORMATION TO SHOW CODE COMPLIANCE IN
 ANOTHER FORMAT.NOTE THAT THE ANCHOR SPACING ON PAGE 2
 WAS BLANK.ALSO, THE SHUTTER CONNECTION MOUNTING TYPE
 SHOULD CORRELATE WITH THE DETAIL MARKERS ON THE ANCHOR
 SCHEDULE; IN THIS CASE, A THROUGH L.IT APPEARS THAT
 YOU ARE USING A (12).
  
 YOU ARE SPECIFYING A 3" EDGE DISTANCE.YOU HAVE
 WRITTEN "HV 12" ON THE INSTALLATION SCHEDULE.THE
 ANCHOR SCHEDULE ON THE PRODUCT APPROVAL USES A THROUGH
 L FOR SHUTTER CONNECTION MOUNTING TYPES.YOU HAVE
 CIRCLED BOTH A AND H ON THE PRODUCT APPROVAL.3" EDGE
 DISTANCE REQUIRES A FACTOR OF .83, SEE SHEET 14 OF THE
 PRODUCT APPROVAL.TAPCON, 8' SPAN, 3" EDGE DISTANCE,
 CONNECTION H REQUIRES 8.5 X .83 SPACING, YOUR
 INSTALLATION SCHEDULE STATES 8".
  
 PLEASE REVISE INSTALLATION SCHEDULE.