| Plan Review Notes For Permit 07070210 |
| Permit Number |
07070210 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2007-08-15 07:52:19 | ****CORRECTIONS**** | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | FBC FLORIDA BUILDING CODE 2004 | | | FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL | | | | | | FROM PREVIOUS LIST: | | | | | | | | | _XX_3.COMPLETE THE ATTACHED INSTALLATION SCHEDULE | | | OR PROVIDE ALL INFORMATION TO SHOW CODE COMPLIANCE IN | | | ANOTHER FORMAT.NOTE THAT THE ANCHOR SPACING ON PAGE 2 | | | WAS BLANK.ALSO, THE SHUTTER CONNECTION MOUNTING TYPE | | | SHOULD CORRELATE WITH THE DETAIL MARKERS ON THE ANCHOR | | | SCHEDULE; IN THIS CASE, A THROUGH L.IT APPEARS THAT | | | YOU ARE USING A (12). | | | | | | YOU ARE SPECIFYING A 3" EDGE DISTANCE.YOU HAVE | | | WRITTEN "HV 12" ON THE INSTALLATION SCHEDULE.THE | | | ANCHOR SCHEDULE ON THE PRODUCT APPROVAL USES A THROUGH | | | L FOR SHUTTER CONNECTION MOUNTING TYPES.YOU HAVE | | | CIRCLED BOTH A AND H ON THE PRODUCT APPROVAL.3" EDGE | | | DISTANCE REQUIRES A FACTOR OF .83, SEE SHEET 14 OF THE | | | PRODUCT APPROVAL.TAPCON, 8' SPAN, 3" EDGE DISTANCE, | | | CONNECTION H REQUIRES 8.5 X .83 SPACING, YOUR | | | INSTALLATION SCHEDULE STATES 8". | | | | | | PLEASE REVISE INSTALLATION SCHEDULE. |
|