Plan Review Notes
Plan Review Notes For Permit 07070203
Permit Number 07070203
Review Stop B
Sequence Number 5
Notes
Date Text
2009-09-21 16:57:104805 S DIXIE HWY/ 07070203
  
 BUILDING PLAN REVIEW
 PERMIT: 07070203
 ADD: 4805 S DIXIE HWY
 CONT: MOUW ASSOCIATES INC
 TEL: (561)715-0845
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVISION# 1 REVIEW
 ACTION: DENIED
 SEPT. 21/ 2009
  
 1) SHEET A3.01 & A3.02 DETAIL# 3. THE NORTH WALL OF THE
 BUILDING SETS WITHIN A FOOT OF THE PROPERTY LINE, WITH
 2 STOREFRONT OPENINGS, TABLE 602 WILL REQUIRE THIS WALL
 TO BE A 3HR RATED WALL AND TABLE 704.8 INDICATES THERE
 CAN BE NO OPENINGS.
  
 2) SHEET A7.01:
  
 2A) PLANS INDICATE THE USE OF A C10 X 25 CHANNEL TO BE
 MOUNTED TO THE EXISTING BEARING BLOCK WALL, AND TO BE
 GROUTED, WHAT STRENGTH WILL THE DESIGN MIX BE? COURSE
 OR FINE GROUT?
  
 2B) THE PLANS INDICATE THE C10 X 25 CHANNEL BUT THERE
 ARE TWO UNKNOWNS:
 1) HOW FAR DOES THE CHANNEL GO PAST THE COLUMN LINE.
 2) WHERE DOES THE FIRST EMBED START FROM THE END OF THE
 C- CHANNEL.
  
 3) SHEET A7.01; 106.1.2 ADDITIONAL INFORMATION
 REQUIRED, 1609.1.2, & RULE 9B-72.
  
 3A) IN DETAIL 2 & 3 IS ILLUSTRATED A INSET ALCOVE WITH
 STEEL STUD CEILING JOIST. THE PLANS INDICATE A STEEL
 ANGLE 1 1/2" X 11/2" X 1/4" @ 4'-0" O.C. THE PLANS LACK
 THE ATTCHMENT METHOD
 AT THE STEEL ANGLE HEADER NOR DO THEY PROVIDE DETAIL AT
 THE BAR JOIST, WHAT HAPPENS IF THE BAR JOIST DO NOT
 LINE UP WITH THE FOUR FT ON CENTER?
  
 3B) THE SECOND ISSUE IS THE STEEL ANGLE HEADER NO
 SIZING INFORMATION HAS BEEN PROVIDED, THE ONLY DETAIL
 PROVIDED IS THE BACK WALL, THE PLANS DO NOT PROVIDE A
 CUT SECTION THROUGH THE SIDE WALL OF THE ALCOVE TO SEE
 IF THE HEADER IS CONTINIOUS AND WHAT TYPE OF BRACING IS
 REQUIRED FROM THE BAR JOIST FOR LATERAL SUPPORT.
  
 3C) THE DETAIL ALSO DOES NOT INDICATE THE USE OF ANY
 CORNER POST MAKING THE ALCOVE HANG INDEPNDENTLY FROM
 THE STRUCTURAL ELEMENTS LOCATED ABOVE THE NEW ALCOVE
 FRAMING. WHILE SHEET A9.01 DOES INDICATE A 90 DEGREE
 OUTSIDE CORNER THE PLANS NOR ANY PRODUCT APPROVALS
 INDICATE ANY INSIDE CORNERS WITH THE SILL AND HEADER
 LOCATED WITHIN THE INTERIOR SPACE. PLEASE PROVIDE
 PRODUCT TESTING INDICATING LARGE MISSILE TESTING AS
 WELL AS WIND PRESSURE. SHEET 18, 19 & 19A ALL INDICATE
 WHERE TTHE EXTERIOR OF THE WINDOW FRAME IS LOCATED
 MAKING THE DETAIL A OUTSIDE OR EXTERIOR CORNER WITH THE
 FRAMING LOCATED WITHIN THE TENANT SPACE.
  
 3D) WITHIN THE PRODUCT APPROVAL (NOA 08-1104.03) PLEASE
 INDICATE THE GLAZING OPTION AND MULLION FOR THIS
 EFFECTS THE SIZE AND PRESSURE OF THE WINDOW OPENINGS.
  
 4) THE SCOPE OF WORK HAS DRAMATICALLY CHANGED PLEASE
 UPDATE THE VALUE OF WORK TO BE COMPLETED UNDERTHIS
 PERMIT. W P B ADMINISTRTIVE CODE 108.2 SCHEDULE OF
 PERMIT FEES. ON BUILDINGS, STRUCTURES, ELECTRICAL, GAS,
 MECHANICAL, AND PLUMBING SYSTEMS OR ALTERATIONS
 REQUIRING A PERMIT, A FEE FOR EACH PERMIT SHALL BE PAID
 AS REQUIRED, IN ACCORDANCE WITH THE SCHEDULE
 ESTABLISHED BY THE APPLICABLE GOVERNING AUTHORITY.
  
 108.3* BUILDING PERMIT VALUATION.
 IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE
 CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE,
 ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS
 APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE
 PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE
 STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR
 FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR
 BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING
 COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFRENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC) WITH REGIONAL ADJUSTMENTS
 FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE
 CONGRESS.
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 STARTING AUGUST 21, 2009, THE CONSTRUCTION SERVICES
 DEPARTMENT WILL BE CLOSED ON FRIDAYS UNTIL FURTHER
 NOTICE.
  
 OPENING HOURS MONDAY - THURSDAY WILL REMAIN AT 8:00 AM
 - 5:00 PM.
  
 JIM WITMER C. B. O.
 COMMERCIAL COMBINATION PLAN REVIEW
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
 SURVEY:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  