Review Stop FIRE
Sequence Number 3
Notes
Date Text
2008-04-21 11:10:25*****DENIED*****
  
 *THE FOLLOWING COMMENTS TAKEN FROM THE PREVIOUS FIRE
 PLAN STILL NEED TO BE ADDRESSED:
  
  
 5. ON THE APPROPIATE EXTERIOR ELEVATION WHICH FRONTS
 SOUTH DIXIE HIGHWAY, POST THE NUMERICAL ADDRESS(ES) ON
 THE BUILDING. AS PER WEST PALM BEACH CODE, ADDRESS
 NUMBERS SHALL BE NO LESS THAN 6" IN HEIGHT AND NO LESS
 THAN 1" IN WIDTH. IF THERE ARE REAR DOORS FOR THESE
 TENANT SPACES, 3" IN HEIGHT AND 1" IN WIDTH NUMBERS
 SHALL BE REQUIRED ON THE REAR DOORS. * SHOW/DISPLAY THE
 ACTUAL NUMBERS
  
 *NEW COMMENT:
  
 A. IF THIS STRUCTURE IS TO BE FIRE PROTECTED AS PER THE
 SPRINKLER AND FIRE ALARM NOTE ON SHEET A1.01, PROVIDE A
 LAYOUT OF THE FIRE ALARM/FIRE SPRINKLER SYSTEM FOR THIS
 SITE. * A SPRINKLER LAYOUT WAS PROVIDED, HOWEVER NO
 NUMERICAL ADDRESS IN THE TITLE BLOCK OF THESE SUBMITTED
 FP SHEETS * COULD NOT LOCATE THE FIRE ALARM LAYOUT AS
 PER YOUR RESPONSE
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE ON THE PLAN EACH ITEM WAS
 ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722