| 2008-04-08 09:42:52 | ** DENIED 3RD REVIEW ** |
| | |
| | ** PLEASE SEE SOME ITEMS FROM PREVIOUS REVIEW ARE STILL |
| | IN NEED OF ADDRESSING. |
| | |
| | 1) NOTE: PLEASE SEE THE SUBMITTED ENERGY CALCULATIONS |
| | ARE STILL BEING SUBMITTED FOR METHOD *A* WHICH IS FOR |
| | WHOLE BUILDING COMPLIANCE. HOW IS THIS POSSIBLE WHEN |
| | THE SCOPE OF WORK IS NOT FOR THE WHOLE BUILDING? PLANS |
| | STILL SHOW SEVERAL ITEMS ARE STILL SHOWN AS EXISTING OR |
| | AREAS WHICH ARE NOT TO BE INCLUDED IN WORK. |
| | PLEASE KNOW THAT IN ORDER TO USE METHOD A, ALL BUILDING |
| | COMPONENTS MUST BE KNOWN, INSERTED AND MEETING CURRENT |
| | MINIMUM CODES. THIS IS NOT THE CASE ON THE CALCULATIONS |
| | SUBMITTED. |
| | PLEASE SEE RESPONSE AS THIS SPECIFICALLY SPEAKS OF A |
| | *SHELL* BUILDING. PLEASE SEE 13-101.1.6 WHICH IS FOR |
| | SHELL BUILDINGS AND IT DOES NOT PERMIT THE USE OF |
| | METHOD *A* YET METHOD *A* IS STILL BEING SUBMITTED. |
| | PLEASE SEE 13-101.1.3, 13-400.0.C.4,13-400.0.B, |
| | 13-400.3.B, 13-400.3.C, 13-415.2, 13-415.2.ABC.1.1, |
| | .1.2 AND .1.3. |
| | PLEASE ALSO KNOW AS NOTED IN SECTIONS ABOVE THE VERSION |
| | SUBMITTED IS 3.0 WHICH IS NOT YET ADOPTED PER FBC. |
| | PLEASE SEE FBC 13-400.3.B, C AND EVEN A AS THIS SHOULD |
| | BE "VERSION" 2.5 WHICH INCORPORATES ENERGY GAUGE SUMMIT |
| | VERSIONS 3.0-3.14 WHICH ARE GENERATED BY VERSION 2.5. |
| | PLEASE SEE THERE ARE SEVERAL ITEMS ON PLANS WHICH DO |
| | NOT CORRELATE WITH THE SUBMITTED CALCULATIONS. |
| | FOR EXAMPLES: |
| | ** NOT WHOLE BUILDING. |
| | |
| | ** PLEASE SEE THE EXTERIOR LIGHTING ON PLANS AND EVEN |
| | ON SHEET E-2.1 DOES NOT CORRELATE WITH THE INPUT DATA |
| | REPORT OR SUMMARY SHEETS. THIS TABLE ON PLANS ALSO |
| | SHOWS A TABLE FOR METHOD B SPACE BY SPACE FOR EXTERIOR |
| | ONLY. IN EITHER CASE PLANS OR LIGHTING AS SHOWN DOES |
| | NOT CORRELATE WITH THE SUBMITTED CALCULATIONS. |
| | |
| | ** PLEASE SEE THE LIGHTING INFORMATION ON THE EXTERIOR |
| | FIXTURES ON THE INPUT DATA REPORT ALSO DOES NOT |
| | CORRELATE WITH THE SUMMARY SHEETS SUBMITTED IN THE SAME |
| | CALCULATIONS. |
| | |
| | ** NO FIXTURE LEGEND ON PLANS. |
| | |
| | ** PLEASE SEE FOR ANOTHER EXAMPLE THE INPUT DATA |
| | REPORT/ENERGY CALCULATIONS SUBMITTED ARE NOT COMPLETE: |
| | SEE *DOORS* AS THIS SECTION IN BLANK AND CONTAINS NO |
| | INFORMATION. PLEASE LOOK FOR COMMENTS FROM OTHER TRADES |
| | FOR THIS ITEM AS THIS IS BEING GIVEN FOR INFORMATION. |
| | ALL BUILDING COMPONENTS AS WELL AS ELECTRICAL ETC ON |
| | PLANS SHALL COORDINATE WITH CALCULATIONS SUBMITTED. |
| | |
| | ** THESE ITEMS ABOVE GIVEN AS SOME EXAMPLES AND IS IN |
| | NO WAY ALL ITEMS WHICH REQUIRE ATTENTION. |
| | NOTE #64 ON SHEET E-0.1 STATES ALL LIGHTING SHOWN IN |
| | COMPLIANCE WITH FBC AND CHAPTER 13. IT IS UNCLEAR WHERE |
| | THE MINIMUM CODE COMPLIANCE DETAILS ARE AT THIS TIME ON |
| | PLANS. |
| | |
| | 2) NOTE: ONCE AGAIN PLEASE CORRELATE SCOPE OF WORK AS |
| | ELECTRICAL PLANS SHOW WORK BEING DONE IN ADJACENT SPACE |
| | YET ARCHITECTURAL PLANS SPECIFICALLY MAKE NOTES TO * NO |
| | DEMO WORK*, * EXISTING TO REMAIN* ETC. |
| | |
| | 3) NOTE: PLEASE SEE NO LIGHTING CONTROLS ADDED TO PLANS |
| | PER 13-415.1.ABC.1.1, .1.2, .1.3 AND .1.4 |
| | A NOTE WAS ADDED FOR EXTERIOR LIGHTING HOWEVER NO TIME |
| | CLOCK ETC WAS SHOWN. |
| | PLEASE SEE NO OTHER LIGHTING CONTROLS WERE LOCATED ON |
| | PLANS AND NOT SHOWN ONCE AGAIN. |
| | |
| | 4) NOTE: PLEASE VERIFY THE ADDITIONAL METER AND WHAT |
| | APPEARS TO BE A SERVICE AND PANELS NOW SHOWN ON THE |
| | WEST ELEVATION ON BUILDING INCLUDING THE INTERIOR WALL |
| | OF THE WEST ELEVATION. THESE ARE NO LABELED AND ARE NOT |
| | ON THE RISER. |
| | FBC 106.1.2 AND 106.3.5.1.2 FOR ADDITIONAL INFORMATION |
| | AND COORDINATION AS ADOPTED PER THE CITY OF WEST PALM |
| | BEACH. |
| | |
| | 5) NOTE: PLEASE SEE FS 553.80(2) (B) WITH RESPECT TO |
| | REPEAT COMMENTS FOR CODE COMPLIANCE. |
| | THE FOLLOWING SECTIONS OF THE CODE WERE GIVEN IN THREE |
| | REVIEWS AND PLANS DO NOT SHOW COMPLIANCE AND IN SOME |
| | CASES NO CHANGES HAVE BEEN MADE TO PLANS. |
| | 13-415.1.ABC.1.1, .1.2, .1.3,.1.4 AND 13-415.2 WERE |
| | GIVEN IN ALL THREE REVIEWS. |
| | PLEASE SEE THE STATUTORY REQUIRED FEE IS NOW ASSESSED |
| | DUE TO THESE SAME SECTIONS BEING REPEATED. THIS IS NOT |
| | A FEE REQUIRED BY LOCAL RULING; THIS IS A REQUIRED FEE |
| | PER STATUTE GIVEN ABOVE. |
| | THE FEE OF $4,920 WILL BE DUE BEFORE PLANS MAY BE |
| | RESUBMITTED. THE STATUTE REQUIRES THE FEE TO BE PAID |
| | BEFORE PLANS MAY BE RESUBMITTED. |
| | ** ONE SET OF ELECTRICAL PLANS AND CALCULATIONS ARE |
| | BEING RETAINED BY THIS OFFICE. |
| | |
| | |
| | ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY |
| | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE |
| | DO NOT HESITATE IN CONTACTING THIS OFFICE. |
| | PLEASE SEE BELOW FOR CONTACT INFORMATION. |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| | LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| | DELAYS. |
| | |