Date Text
2008-04-08 09:42:52** DENIED 3RD REVIEW **
  
 ** PLEASE SEE SOME ITEMS FROM PREVIOUS REVIEW ARE STILL
 IN NEED OF ADDRESSING.
  
 1) NOTE: PLEASE SEE THE SUBMITTED ENERGY CALCULATIONS
 ARE STILL BEING SUBMITTED FOR METHOD *A* WHICH IS FOR
 WHOLE BUILDING COMPLIANCE. HOW IS THIS POSSIBLE WHEN
 THE SCOPE OF WORK IS NOT FOR THE WHOLE BUILDING? PLANS
 STILL SHOW SEVERAL ITEMS ARE STILL SHOWN AS EXISTING OR
 AREAS WHICH ARE NOT TO BE INCLUDED IN WORK.
 PLEASE KNOW THAT IN ORDER TO USE METHOD A, ALL BUILDING
 COMPONENTS MUST BE KNOWN, INSERTED AND MEETING CURRENT
 MINIMUM CODES. THIS IS NOT THE CASE ON THE CALCULATIONS
 SUBMITTED.
 PLEASE SEE RESPONSE AS THIS SPECIFICALLY SPEAKS OF A
 *SHELL* BUILDING. PLEASE SEE 13-101.1.6 WHICH IS FOR
 SHELL BUILDINGS AND IT DOES NOT PERMIT THE USE OF
 METHOD *A* YET METHOD *A* IS STILL BEING SUBMITTED.
 PLEASE SEE 13-101.1.3, 13-400.0.C.4,13-400.0.B,
 13-400.3.B, 13-400.3.C, 13-415.2, 13-415.2.ABC.1.1,
 .1.2 AND .1.3.
 PLEASE ALSO KNOW AS NOTED IN SECTIONS ABOVE THE VERSION
 SUBMITTED IS 3.0 WHICH IS NOT YET ADOPTED PER FBC.
 PLEASE SEE FBC 13-400.3.B, C AND EVEN A AS THIS SHOULD
 BE "VERSION" 2.5 WHICH INCORPORATES ENERGY GAUGE SUMMIT
 VERSIONS 3.0-3.14 WHICH ARE GENERATED BY VERSION 2.5.
 PLEASE SEE THERE ARE SEVERAL ITEMS ON PLANS WHICH DO
 NOT CORRELATE WITH THE SUBMITTED CALCULATIONS.
 FOR EXAMPLES:
 ** NOT WHOLE BUILDING.
  
 ** PLEASE SEE THE EXTERIOR LIGHTING ON PLANS AND EVEN
 ON SHEET E-2.1 DOES NOT CORRELATE WITH THE INPUT DATA
 REPORT OR SUMMARY SHEETS. THIS TABLE ON PLANS ALSO
 SHOWS A TABLE FOR METHOD B SPACE BY SPACE FOR EXTERIOR
 ONLY. IN EITHER CASE PLANS OR LIGHTING AS SHOWN DOES
 NOT CORRELATE WITH THE SUBMITTED CALCULATIONS.
  
 ** PLEASE SEE THE LIGHTING INFORMATION ON THE EXTERIOR
 FIXTURES ON THE INPUT DATA REPORT ALSO DOES NOT
 CORRELATE WITH THE SUMMARY SHEETS SUBMITTED IN THE SAME
 CALCULATIONS.
  
 ** NO FIXTURE LEGEND ON PLANS.
  
 ** PLEASE SEE FOR ANOTHER EXAMPLE THE INPUT DATA
 REPORT/ENERGY CALCULATIONS SUBMITTED ARE NOT COMPLETE:
 SEE *DOORS* AS THIS SECTION IN BLANK AND CONTAINS NO
 INFORMATION. PLEASE LOOK FOR COMMENTS FROM OTHER TRADES
 FOR THIS ITEM AS THIS IS BEING GIVEN FOR INFORMATION.
 ALL BUILDING COMPONENTS AS WELL AS ELECTRICAL ETC ON
 PLANS SHALL COORDINATE WITH CALCULATIONS SUBMITTED.
  
 ** THESE ITEMS ABOVE GIVEN AS SOME EXAMPLES AND IS IN
 NO WAY ALL ITEMS WHICH REQUIRE ATTENTION.
 NOTE #64 ON SHEET E-0.1 STATES ALL LIGHTING SHOWN IN
 COMPLIANCE WITH FBC AND CHAPTER 13. IT IS UNCLEAR WHERE
 THE MINIMUM CODE COMPLIANCE DETAILS ARE AT THIS TIME ON
 PLANS.
  
 2) NOTE: ONCE AGAIN PLEASE CORRELATE SCOPE OF WORK AS
 ELECTRICAL PLANS SHOW WORK BEING DONE IN ADJACENT SPACE
 YET ARCHITECTURAL PLANS SPECIFICALLY MAKE NOTES TO * NO
 DEMO WORK*, * EXISTING TO REMAIN* ETC.
  
 3) NOTE: PLEASE SEE NO LIGHTING CONTROLS ADDED TO PLANS
 PER 13-415.1.ABC.1.1, .1.2, .1.3 AND .1.4
 A NOTE WAS ADDED FOR EXTERIOR LIGHTING HOWEVER NO TIME
 CLOCK ETC WAS SHOWN.
 PLEASE SEE NO OTHER LIGHTING CONTROLS WERE LOCATED ON
 PLANS AND NOT SHOWN ONCE AGAIN.
  
 4) NOTE: PLEASE VERIFY THE ADDITIONAL METER AND WHAT
 APPEARS TO BE A SERVICE AND PANELS NOW SHOWN ON THE
 WEST ELEVATION ON BUILDING INCLUDING THE INTERIOR WALL
 OF THE WEST ELEVATION. THESE ARE NO LABELED AND ARE NOT
 ON THE RISER.
 FBC 106.1.2 AND 106.3.5.1.2 FOR ADDITIONAL INFORMATION
 AND COORDINATION AS ADOPTED PER THE CITY OF WEST PALM
 BEACH.
  
 5) NOTE: PLEASE SEE FS 553.80(2) (B) WITH RESPECT TO
 REPEAT COMMENTS FOR CODE COMPLIANCE.
 THE FOLLOWING SECTIONS OF THE CODE WERE GIVEN IN THREE
 REVIEWS AND PLANS DO NOT SHOW COMPLIANCE AND IN SOME
 CASES NO CHANGES HAVE BEEN MADE TO PLANS.
 13-415.1.ABC.1.1, .1.2, .1.3,.1.4 AND 13-415.2 WERE
 GIVEN IN ALL THREE REVIEWS.
 PLEASE SEE THE STATUTORY REQUIRED FEE IS NOW ASSESSED
 DUE TO THESE SAME SECTIONS BEING REPEATED. THIS IS NOT
 A FEE REQUIRED BY LOCAL RULING; THIS IS A REQUIRED FEE
 PER STATUTE GIVEN ABOVE.
 THE FEE OF $4,920 WILL BE DUE BEFORE PLANS MAY BE
 RESUBMITTED. THE STATUTE REQUIRES THE FEE TO BE PAID
 BEFORE PLANS MAY BE RESUBMITTED.
 ** ONE SET OF ELECTRICAL PLANS AND CALCULATIONS ARE
 BEING RETAINED BY THIS OFFICE.
  
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717