2007-11-24 16:13:47DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 ****FROM PREVIOUS REVIEW:
  
 1, OK
  
 2. OK
  
 3. SHT A2.02 SUBMIT CALCULATIONS FOR ROOF DRAINAGE PER
 SECTIONS 1106 & 1107 WITH ALL SUBSECTIONS AND TABLES.
 SHOW THE TOTAL SQUARE FOOTAGE OF EACH ROOF AREA ALONG
 WITH 1/2 AREA OF ALL VERTICAL WALLS INCLUDING PARAPETS
 THAT AFFECT EACH AREA ADDED TO EACH ROOF AREA.--
 INDICATE THE SLOPE OF THE ROOF AND THE DIRECTION OF
 SLOPE.--NOTE INDICATES EXISTING ALUM. GUTTER. SHOW
 ALL GUTTERS, AND INDICATE THE SIZE OF THE GUTTERS.
 INDICATE THE SLOPE OF THE GUTTERS SHOWING THE HIGH
 POINTS AND THE LOW POINTS OF THE GUTTERS. TABLE 1106.6.
 --SHOW THE LOCATION OF ALL AND SIZE OF ALL
 DOWNSPOUTS.
 ****NO RESPONSE, NOT ADDRESSED.
  
 4. SHT A3.01 CALL OUT THE LOCATION OF ALL GUTTERS AND
 DOWNSPOUTS ON ELEVATION #3. SECTION 106.1.1. ****NO
 RESPONSE, NOT ADDRESSED
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
 ****NO RESPONSE, NOT ADDRESSED.
  
 **********NEW COMMENT**********
  
 1B. PLEASE CORRECT THE ADDRESS ON THE APPLICATION AND
 ON THE TITLE BLOCK OF EACH SHEET. 4805 S. DIXIE HWY.
 (SEE ELECTRICAL SHEETS).
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]