| Date |
Text |
| 2007-11-24 16:13:47 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 CHAPTER 1 |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | ****FROM PREVIOUS REVIEW: |
| | |
| | 1, OK |
| | |
| | 2. OK |
| | |
| | 3. SHT A2.02 SUBMIT CALCULATIONS FOR ROOF DRAINAGE PER |
| | SECTIONS 1106 & 1107 WITH ALL SUBSECTIONS AND TABLES. |
| | SHOW THE TOTAL SQUARE FOOTAGE OF EACH ROOF AREA ALONG |
| | WITH 1/2 AREA OF ALL VERTICAL WALLS INCLUDING PARAPETS |
| | THAT AFFECT EACH AREA ADDED TO EACH ROOF AREA.-- |
| | INDICATE THE SLOPE OF THE ROOF AND THE DIRECTION OF |
| | SLOPE.--NOTE INDICATES EXISTING ALUM. GUTTER. SHOW |
| | ALL GUTTERS, AND INDICATE THE SIZE OF THE GUTTERS. |
| | INDICATE THE SLOPE OF THE GUTTERS SHOWING THE HIGH |
| | POINTS AND THE LOW POINTS OF THE GUTTERS. TABLE 1106.6. |
| | --SHOW THE LOCATION OF ALL AND SIZE OF ALL |
| | DOWNSPOUTS. |
| | ****NO RESPONSE, NOT ADDRESSED. |
| | |
| | 4. SHT A3.01 CALL OUT THE LOCATION OF ALL GUTTERS AND |
| | DOWNSPOUTS ON ELEVATION #3. SECTION 106.1.1. ****NO |
| | RESPONSE, NOT ADDRESSED |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID |
| | SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY |
| | ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU |
| | FOR YOUR ANTICIPATED COOPERATION. |
| | ****NO RESPONSE, NOT ADDRESSED. |
| | |
| | **********NEW COMMENT********** |
| | |
| | 1B. PLEASE CORRECT THE ADDRESS ON THE APPLICATION AND |
| | ON THE TITLE BLOCK OF EACH SHEET. 4805 S. DIXIE HWY. |
| | (SEE ELECTRICAL SHEETS). |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |