Plan Review Notes
Plan Review Notes For Permit 07070203
Permit Number 07070203
Review Stop M
Sequence Number 2
Notes
Date Text
2007-10-23 14:30:54PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) SEE ENERGY CALCULATIONS ARE ON FORM 400A, SEE
 13-400.0.C.4 RENOVATED BUILDINGS MAY ONLY USE FORM B OR
 C. ALSO SEE 13-400.2.A.2 SHELL BUILDING MAY ONLY USE
 FORM B OR C. PLEASE CORRECT.
  
 2) SEE ENERGY CALCULATIONS SHOW THIRTEEN A/C SYSTEMS,
 PLANS SHOW ONLY SEVEN A/C SYSTEMS. WHEN REDOING ENERGY
 CALCULATIONS "SYSTEM REPORT" ONLY DO FOR 4805 S. DIXIE
 HWY. SUITES 105 THROUGH 109. PLEASE COORDINATE ALL
 CHANGES WITH ARCHITECT AND MECHANICAL ENGINEER.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]