Plan Review Notes
Plan Review Notes For Permit 07070203
Permit Number 07070203
Review Stop E
Sequence Number 2
Notes
Date Text
2007-10-16 13:05:31 
 *** DENIED 2ND REVIEW ***
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW ARE STILL
 IN NEED OF ADDRESSING.
  
  
 1) NOTE: PLEASE SEE THE ADDRESS ON THE TITLE BLOCKS ON
 ARCHITECTURAL SHEETS CALL FOR 4805 S DIXIE, THE
 ELECTRICAL PLANS CALL FOR 4801-4815 AND PERMIT
 APPLICATION STILL INDICATES 4805-4815.
 PLEASE CORRELATE ALL AND SEE COMMENTS FOR ADDRESSING.
 PLEASE ADJUST TITLE BLOCKS AS NEEDED. ** SHEETS WHICH
 DO NOT NEED REVISIONS FOR OTHER COMMENTS, THIS MAY DONE
 BY OTHER MEANS.
 IF THERE ARE ANY QUESTIONS, PLEASE CONTACT THIS
 OFFICE.
  
 2) NOTE: PLEASE SUBMIT INTERIOR LIGHTING PERFORMANCE
 CALCULATIONS. 13-415.2 HOW IS METHOD *A* BEING
 SUBMITTED FOR A SHELL BUILDING WHICH IS EXISTING?
 PLEASE SEE MECHANICAL REVIEW COMMENTS.
  
 3) NOTE: PLEASE CLARIFY THE METHOD OF CONTROL FOR
 LIGHTING PER 13-415.1.ABC.1.1, .1.2 AND .1.3
 PLEASE SEE THE TYPE OF TIME CLOCK REQUIRED FOR EXTERIOR
 LIGHTING NEED TO BE CLARIFIED. NOT SHOWN ON PLANS.
 PLEASE SEE 13-415.1.ABC.1.4
  
 4) NOTE: PLEASE SEE PREVIOUS REVIEW COMMENT #9 WHICH
 COMMENTED ON THE DISTANCE THE GUTTER WOULD BE IN FRONT
 OF ELECTRICAL EQUIPMENT. THE PLANS ARE NOW SHOWN WITH A
 NOTE WHICH MENTIONS TO MEET CODE. PLEASE PROVIDE A
 MOUNTING/RACK DETAIL AS ALL METER, MAINS EQUIPMENT WILL
 BE MOUNTED OFF THE WALL BY A SUBSTANTIAL DISTANCE.
 ** PREVIOUS NOTE **
 PLEASE SEE THE GUTTER SIZES ARE SHOWN WHICH APPEAR TO
 EXCEED THE DISTANCE IN FRONT OF THE ELECTRICAL SERVICE
 EQUIPMENT PER 110.26A3
  
  
 ** PLEASE SEE COMMENTS FROM OTHER TRADES WHICH WILL
 AFFECT PLANS, SUBMITTED DOCUMENTS AND ELECTRICAL
 PLANS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]