Plan Review Notes
Plan Review Notes For Permit 07070203
Permit Number 07070203
Review Stop M
Sequence Number 1
Notes
Date Text
2007-07-26 10:53:35*** DENIED ***
 1) MECHANICAL PLAN PAGE MP-0.1 MECHANICAL NOTE #2
 STATES THE LATEST EDITION OF THE FBC, PLEASE CHANGE TO
 THE 2004 WITH 2006 REVISIONS FBC.
  
 2) PLEASE STATE ON PLANS PAGE MP-1.2 WERE THE 2" A/C
 CONDENSATE LINE WILL DISCHARGE TO.
  
 3) PLEASE SUBMIT ENERGY CALCULATIONS. 2004 FBC
 13-101.1.6 SHELL BUILDINGS.
 NONRESIDENTIAL BUILDINGS THAT ARE PERMITTED PRIOR TO
 DESIGN COMPLETION OR WHICH WILL BE FINISHED IN SECTIONS
 AT A TIME AFTER CONSTRUCTION OF THE SHELL SHALL COMPLY
 WITH EITHER METHOD B OR C OF SUBCHAPTER 13-4 OF THE
 CODE PRIOR TO GRANTING OF A PERMIT TO BUILD. ALL
 ASSUMPTIONS MADE ABOUT FEATURES NOT INSTALLED UNTIL
 LATER THAT ARE NOT ON THE BUILDING PLANS SHALL BE
 LISTED AND APPENDED TO THE COMPLIANCE FORM SUBMITTED TO
 THE BUILDING DEPARTMENT. UNLESS THE BUILDING IS
 COMPLETED AS PER ALL ASSUMPTIONS MADE IN THE ORIGINAL
 CODE COMPLIANCE SUBMITTAL, A REVISED CODE SUBMITTAL(S)
 USING METHODS A, B OR C SHALL BE SUBMITTED WHEN
 COMPLETION OF THE BUILDING (OR PART OF THE BUILDING) IS
 PERMITTED.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.
  