| 2007-07-24 12:16:15 | *** UNSAT *** |
| | |
| | 1) NOTE: PLEASE SEE THE SPACE ON THE PERMIT APPLICATION |
| | WHICH REQUIRES THE DESCRIPTION OF THE PROJECT TO BE IN |
| | DETAIL. PLEASE SEE THIS MENTIONS *EXTERIOR IMPROVEMENTS |
| | AND RE-ROOF* HOWEVER THE SCOPE OF WORK AS PLACE DON |
| | PLANS FAR EXCEED THIS STATEMENT. |
| | PLEASE ADJUST PERMIT APPLICATION. |
| | |
| | 2) NOTE: PLEASE SEE THE PLANS CALL FOR THIS AS A LEVEL |
| | 2 ALTERATION PER FBC EXISTING BUILDING CODE. PLEASE |
| | VERIFY THIS AND SEE BUILDING REVIEW COMMENTS ALONG WITH |
| | OTHER TRADES AS THIS BUILDING IS NOT EXISTING AS A |
| | SHELL FOR FUTURE BUILD OUTS. |
| | FBC 106.1.2 |
| | |
| | 3) NOTE:PLEASE KNOW THAT ANY PERMIT APPLICATIONS |
| | WHICH ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES |
| | PROJECTS UNDER THE NEW CODES ADOPTED BY THE STATE. |
| | PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO |
| | THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70. |
| | PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY |
| | AFFECT DESIGNS FOR ALL TRADES. |
| | PLEASE SEE THE ARCHITECTURAL SHEETS WHICH ARE LISTING |
| | SOME OTHER CODES THAN WHAT IS IN EFFECT AT THIS TIME |
| | AND ALSO SHOWS SOME OTHER SECTIONS NOT CURRENTLY IN |
| | EFFECT. |
| | PLEASE SEE PLANS WHICH STATE 2004 FBC MAY NOT BE |
| | ACCURATE AS THERE HAVE BEEN REVISIONS TO THE CODE FOR |
| | OTHER ADOPTED CODES. THIS IS WHY THESE SHOULD STATE THE |
| | 2006 REVISION TO THE 2004 FBC. |
| | PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS |
| | REVIEWER AT A MINIMUM. |
| | 2004 FBC W/ 2006 REVISIONS |
| | 2005 NFPA-70 |
| | 2002 NFPA-72 (WHEN IN DESIGN) |
| | 2003 NFPA-101 |
| | |
| | |
| | 4) NOTE: PLEASE SEE THAT PLANS AND APPLICATION WILL BE |
| | ROUTED TO THE ADDRESSING REVIEWER. ONCE THE CORRECT |
| | ADDRESS(S) AND/OR SUITE HAVE BEEN DETERMINED PLEASE |
| | ADJUST AND CORRECT TITLE BLOCKS. |
| | FAC 61G15-23.002, FAC 61G1-16.004 |
| | |
| | 5) NOTE: PLEASE SUBMIT ENERGY CALCULATIONS FOR THE |
| | BUILDING AS REQUIRED PER 13-415.1.AB.1.1, 13-415.1.B. |
| | 13-415.1.C,AND 13-415.2 FOR PERFORMANCE. EXTERIOR |
| | LIGHTING, 13-415.2.ABC.1.3, (TABLE). PLEASE SEE THIS IS |
| | BEING DONE AS A SHELL AND METHOD OF CALCULATIONS ARE |
| | SPECIFIC. |
| | |
| | 6) NOTE: PLEASE SEE AS MINIMUM LIGHTING PER THE |
| | FOLLOWING COMMENT WILL BE REQUIRED ON THE INTERIOR OF |
| | THE SHELL BUILDING PLEASE SEE THAT LIGHTING CONTROLS OF |
| | SOME KIND WILL BE REQUIRED PER 13-415.1.ABC.1.1, .1.2 |
| | AND .1.3 |
| | PLEASE SEE THE TYPE OF TIME CLOCK REQUIRED FOR EXTERIOR |
| | LIGHTING NEED TO BE CLARIFIED. |
| | PLEASE SEE 13-415.1.ABC.1.4 |
| | |
| | 7) NOTE: PLEASE SEE FIRE MARSHAL AND LIFE SAFETY CODE |
| | REQUIRES MINIMUM LIGHTING INSIDE SHELL SPACE AND EXIT |
| | LIGHTING REQUIRED PER FIRE MARSHAL AND LIFE SAFETY |
| | CODE. |
| | PLEASE ADJUST PLANS TO INCLUDE ALONG WITH SOME SORT OF |
| | BATTERY BACK UP FIXTURES. |
| | LS 101 7.8, 7.9 |
| | |
| | 8) NOTE: PLEASE SEE THE RISER APPEARS TO SHOW THE |
| | LOCATIONS OF THE MAINS TOO HIGH. PLEASE SEE 110.26, |
| | 230.70, 404.8A. |
| | PLEASE PROVIDE THE ELEVATIONS OF THE EQUIPMENT AS SHOWN |
| | ON RISER. |
| | |
| | 9) NOTE: PLEASE SEE THE GUTTER SIZES ARE SHOWN WHICH |
| | APPEAR TO EXCEED THE DISTANCE IN FRONT OF THE |
| | ELECTRICAL SERVICE EQUIPMENT PER 110.26A3 |
| | |
| | 10) NOTE: PLEASE SEE THE RISER SHOWS *STRUCTURAL STEEL* |
| | AS PART OF THE GROUNDING ELECTRODE SYSTEM. PLEASE |
| | CLARIFY METHODS. PLEASE SEE THIS IS AN EXISTING |
| | BUILDING AND UNLESS THE EXISTING FOOTER STEEL IS |
| | ALREADY A PART OF THE SYSTEM, THE EXISTING FOOTER STEEL |
| | IS NOT REQUIRED TO BE PART AS THIS WOULD AFFECT THE |
| | STRUCTURAL INTEGRITY OF THE FOOTER. |
| | 250.50 |
| | |
| | 11) NOTE: PLEASE SEE THAT IN NO CASE MAY *WHITE-OUT* BE |
| | USED ON PLANS. |
| | FS 471/481 |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| 2007-07-23 16:19:39 | PLANS REMOVED FROM INCOMING IN ELECTRICAL FOR REVIEW. |
| | PLANS WILL BE RETURNED TO INCOMING WAITING FOR COMM |
| | BOARD ONCE REVIEW IS COMPLETED. |