Plan Review Notes
Plan Review Notes For Permit 07070203
Permit Number 07070203
Review Stop E
Sequence Number 1
Notes
Date Text
2007-07-24 12:16:15*** UNSAT ***
  
 1) NOTE: PLEASE SEE THE SPACE ON THE PERMIT APPLICATION
 WHICH REQUIRES THE DESCRIPTION OF THE PROJECT TO BE IN
 DETAIL. PLEASE SEE THIS MENTIONS *EXTERIOR IMPROVEMENTS
 AND RE-ROOF* HOWEVER THE SCOPE OF WORK AS PLACE DON
 PLANS FAR EXCEED THIS STATEMENT.
 PLEASE ADJUST PERMIT APPLICATION.
  
 2) NOTE: PLEASE SEE THE PLANS CALL FOR THIS AS A LEVEL
 2 ALTERATION PER FBC EXISTING BUILDING CODE. PLEASE
 VERIFY THIS AND SEE BUILDING REVIEW COMMENTS ALONG WITH
 OTHER TRADES AS THIS BUILDING IS NOT EXISTING AS A
 SHELL FOR FUTURE BUILD OUTS.
 FBC 106.1.2
  
 3) NOTE:PLEASE KNOW THAT ANY PERMIT APPLICATIONS
 WHICH ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES
 PROJECTS UNDER THE NEW CODES ADOPTED BY THE STATE.
 PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO
 THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70.
 PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY
 AFFECT DESIGNS FOR ALL TRADES.
 PLEASE SEE THE ARCHITECTURAL SHEETS WHICH ARE LISTING
 SOME OTHER CODES THAN WHAT IS IN EFFECT AT THIS TIME
 AND ALSO SHOWS SOME OTHER SECTIONS NOT CURRENTLY IN
 EFFECT.
 PLEASE SEE PLANS WHICH STATE 2004 FBC MAY NOT BE
 ACCURATE AS THERE HAVE BEEN REVISIONS TO THE CODE FOR
 OTHER ADOPTED CODES. THIS IS WHY THESE SHOULD STATE THE
 2006 REVISION TO THE 2004 FBC.
 PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS
 REVIEWER AT A MINIMUM.
 2004 FBC W/ 2006 REVISIONS
 2005 NFPA-70
 2002 NFPA-72 (WHEN IN DESIGN)
 2003 NFPA-101
  
  
 4) NOTE: PLEASE SEE THAT PLANS AND APPLICATION WILL BE
 ROUTED TO THE ADDRESSING REVIEWER. ONCE THE CORRECT
 ADDRESS(S) AND/OR SUITE HAVE BEEN DETERMINED PLEASE
 ADJUST AND CORRECT TITLE BLOCKS.
 FAC 61G15-23.002, FAC 61G1-16.004
  
 5) NOTE: PLEASE SUBMIT ENERGY CALCULATIONS FOR THE
 BUILDING AS REQUIRED PER 13-415.1.AB.1.1, 13-415.1.B.
 13-415.1.C,AND 13-415.2 FOR PERFORMANCE. EXTERIOR
 LIGHTING, 13-415.2.ABC.1.3, (TABLE). PLEASE SEE THIS IS
 BEING DONE AS A SHELL AND METHOD OF CALCULATIONS ARE
 SPECIFIC.
  
 6) NOTE: PLEASE SEE AS MINIMUM LIGHTING PER THE
 FOLLOWING COMMENT WILL BE REQUIRED ON THE INTERIOR OF
 THE SHELL BUILDING PLEASE SEE THAT LIGHTING CONTROLS OF
 SOME KIND WILL BE REQUIRED PER 13-415.1.ABC.1.1, .1.2
 AND .1.3
 PLEASE SEE THE TYPE OF TIME CLOCK REQUIRED FOR EXTERIOR
 LIGHTING NEED TO BE CLARIFIED.
 PLEASE SEE 13-415.1.ABC.1.4
  
 7) NOTE: PLEASE SEE FIRE MARSHAL AND LIFE SAFETY CODE
 REQUIRES MINIMUM LIGHTING INSIDE SHELL SPACE AND EXIT
 LIGHTING REQUIRED PER FIRE MARSHAL AND LIFE SAFETY
 CODE.
 PLEASE ADJUST PLANS TO INCLUDE ALONG WITH SOME SORT OF
 BATTERY BACK UP FIXTURES.
 LS 101 7.8, 7.9
  
 8) NOTE: PLEASE SEE THE RISER APPEARS TO SHOW THE
 LOCATIONS OF THE MAINS TOO HIGH. PLEASE SEE 110.26,
 230.70, 404.8A.
 PLEASE PROVIDE THE ELEVATIONS OF THE EQUIPMENT AS SHOWN
 ON RISER.
  
 9) NOTE: PLEASE SEE THE GUTTER SIZES ARE SHOWN WHICH
 APPEAR TO EXCEED THE DISTANCE IN FRONT OF THE
 ELECTRICAL SERVICE EQUIPMENT PER 110.26A3
  
 10) NOTE: PLEASE SEE THE RISER SHOWS *STRUCTURAL STEEL*
 AS PART OF THE GROUNDING ELECTRODE SYSTEM. PLEASE
 CLARIFY METHODS. PLEASE SEE THIS IS AN EXISTING
 BUILDING AND UNLESS THE EXISTING FOOTER STEEL IS
 ALREADY A PART OF THE SYSTEM, THE EXISTING FOOTER STEEL
 IS NOT REQUIRED TO BE PART AS THIS WOULD AFFECT THE
 STRUCTURAL INTEGRITY OF THE FOOTER.
 250.50
  
 11) NOTE: PLEASE SEE THAT IN NO CASE MAY *WHITE-OUT* BE
 USED ON PLANS.
 FS 471/481
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-07-23 16:19:39PLANS REMOVED FROM INCOMING IN ELECTRICAL FOR REVIEW.
 PLANS WILL BE RETURNED TO INCOMING WAITING FOR COMM
 BOARD ONCE REVIEW IS COMPLETED.