Plan Review Notes
Plan Review Notes For Permit 07070203
Permit Number 07070203
Review Stop AD
Sequence Number 1
Notes
Date Text
2007-08-08 15:44:504805 S DIXIE HWY/ 07070203
  
 BUILDING PLAN REVIEW
 PERMIT: 07070203
 ADD: 4805 S DIXIE HWY
 CONT: MOUW ASSOCIATES INC
 TEL: (561)715-0845
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT
 ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3) THE PERMIT APPLICATION DESCRIPTION OF PROJECT NEEDS
 TO ACCURATE TO THE WORK THAT IS ILLUSTRATED IN THE
 PLANS, PLEASE CORRECT APPLICATION OR DELETE WORK FROM
 PLAN. 106.1.1*
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 4) THE APPLICATION HAS AN ADDRESS RANGE FROM 4805- 4815
 S DIXIE, THE CITY RECORDS AS WELL AS THE PROPERTY
 APPRAISERS OFFICE LIST THIS PROPERTY UNDER THE PROPERTY
 CONTROL NUMBER AS 4805 S DIXIE, PLEASE CORRECT. IF
 ADDITIONAL SUITE ADDRESSES WILL BE REQUIRED CONTACT
 LILY URSA (MIS DEPARTMENT) AT(561)822-1239.
  
 5) 04.2.1.3 THE BUILDING OFFICIAL MAY SET STANDARDS
 THROUGH DEPARTMENTAL POLICY STANDARDS FOR PLANS AND
 SPECIFICATIONS. "NO WHITE OUT" ALLOWED ON PLANS. SEE
 SHEET A1.01 BOTH IN THE HEADER STRIP AND IN THE BODY OF
 THE PLAN SEE GENERAL PROJECT DATA.
  
 6) SHEET A1.01 PLEASE UPDATE THE CODE REFERENCE TO THE
 2004 FBC BUILDING W/ 2006 AMENDMENTS.
  
 7) PLEASE PROVIDE THE LAST KNOWN OCCUPANCY TYPE?
 106.1.2* ADDITIONAL INFORMATION REQUIRED.
  
 8) THE PERMIT APPLICATION DESCRIPTION OF PROJECT MAY
 NEED TO BE MODIFIED TO SHOW INTENDED USE BUT AS THE
 PLANS INDICATE NOW THIS WILL BE A SINGLE MERCANTILE
 TENANT WITH 22,164 SQ FT WITHIN THE TENANT SPACE.
 PLEASE SEE,903.2.6 GROUP M.
 AN AUTOMATIC SPRINKLER SYSTEM SHALL BE PROVIDED
 THROUGHOUT BUILDINGS CONTAINING A GROUP M OCCUPANCY
 WHERE ONE OF THE FOLLOWING CONDITIONS EXISTS:
 1.WHERE A GROUP M FIRE AREA EXCEEDS 12,000 SQUARE
 FEET (1115 M 2 );
 PLEASE UPDATE PLANS PROVIDING AN AUTOMATIC FIRE
 SPRINKLER SYSTEM OR SPLIT THE BUILDING INTO 2 FIRE
 AREAS EACH LESS THAN 12,000 SQ FT.
 DEFINITION: FIRE AREA. THE AGGREGATE FLOOR AREA
 ENCLOSED AND BOUNDED BY FIRE WALLS, FIRE BARRIERS,
 EXTERIOR WALLS OR FIRE-RESISTANCE-RATED HORIZONTAL
 ASSEMBLIES OF A BUILDING.
  
 9) SHEET A1.01 CODE ANALYSIS INDICATES THIS ALTERATION
 IS TO BE A LEVEL II ALTERATION ,PLEASE SEE 2004 EBC
 EXISTING BUILDING CODE 2006 AMENDMENTS SECTION 707.5.2
  
 A LEVEL III IS WHERE 30 % OF THE TOTAL SUM OF THE FLOOR
 AND ROOF AREAS OF THE BUILDING ARE INVOLVED IN
 STRUCTURAL ALTERATIONS WITHIN A 12-MONTH PERIOD, PLEASE
 CORRECT AND SEE THE REQUIREMENTS OF CHAPTER 7, EXISTING
 BUILDING CODE INCLUSIVE OF 708 ENERGY CONSERVATION.
 708.1 MINIMUM REQUIREMENTS. ALTERATIONS SUBJECT TO THIS
 CHAPTER SHALL COMPLY WITH THE REQUIREMENTS OF CHAPTER
 13 OF THE FLORIDA BUILDING CODE.
  
 10) SHEET A1.01 EGRESS DATA (NEW ADDITION ONLY) WHAT
 PORTION OF THIS WORK IS THE NEW ADDITION?106.1.2
 ADDITIONAL INFORMATION REQUIRED.
  
 11) SHEET A1.01 EGRESS DATA ALSO LISTMERCANTILE AS
 WELL AS AN UNCONCENTRATED ASSEMBLY IS THE PURPOSE OF
 THE ASSEMBLY OCCUPANCY FOR A FUTURE TENANT BUILDOUT?.
  
 12)SHEETS A1.01 AND A2.01 BOTH INDICATE (2) AREAS OF
 CONCERN WITH TABLE 601.
  
 12A) THE NORTH WALL OF THE BUILDING SETS WITHIN A FOOT
 OF THE PROPERTY LINE, WITH 3 STOREFRONT OPENINGS, TABLE
 602 WILL REQUIRE THIS WALL TO BE A 3HR RATED WALL AND
 TABLE 704.8 INDICATES THERE CAN BE NO OPENINGS.
  
 12B) THE SOUTHWEST CORNER OF THE BUILDING WHERE THE
 NEWLY RELOCATED ELECTRIC METER IS LOCATED THIS WALL
 WILL ALSO NEED TO STATE THE DISTANCE FROM THE PROPERTY
 LINE SEE TABLE 602 FOR HOURLY RATINGS.
  
 13) SHEET A2.01 PLEASE PROVIDE THE ACCESS AISLE FOR THE
 HANDICAPPED PARKING SPACE.
 11-4.6.2(1)ALL SPACES MUST BE LOCATED ON AN
 ACCESSIBLE ROUTE NO LESS THAN 44 INCHES (1118 MM)WIDE
 SO THAT USERS WILL NOT BE COMPELLED TO WALK OR WHEEL
 BEHIND PARKED VEHICLES.
  
 14) SHEET A2.02 ROOF PLAN DOESN?T INDICATE ANY ROOF
 DRAINAGE, DIRECTION OF DRAINAGE, PRIMARY OR SECONDARY
 DRAINAGE SYSTEMS. PLEASE PROVIDE ADDITIONAL INFORMATION
 IN REGARDS TO 1503.4 ROOF DRAINAGE.
 UNLESS ROOFS ARE SLOPED TO DRAIN OVER ROOF EDGES,
 DESIGN AND INSTALLATION OF ROOF DRAINAGE SYSTEMS SHALL
 COMPLY WITH THE FLORIDA BUILDING CODE, PLUMBING ,
 CHAPTER 11 .
  
 15) SHEET A2.02 INDICATES NEW AWNINGS, TO BE COVERED
 UNDER A SEPARATE PERMIT WITH ASSOCIATED FEES AND
 REVIEWS. 3202.3 ENCROACHMENTS 8 FEET OR MORE ABOVE
 GRADE.
 ENCROACHMENTS 8 FEET (2438 MM) OR MORE ABOVE GRADE
 SHALL COMPLY WITH SECTIONS 3202.3.1 THROUGH 3202.3.4 .
  
 AWNINGS
 3202.3.1 AWNINGS , CANOPIES, MARQUEES AND SIGNS.
 AWNINGS , CANOPIES, MARQUEES AND SIGNS SHALL BE
 CONSTRUCTED SO AS TO SUPPORT APPLICABLE LOADS AS
 SPECIFIED IN CHAPTER 16 . AWNINGS , CANOPIES, MARQUEES
 AND SIGNS WITH LESS THAN 15 FEET (4572 MM) CLEARANCE
 ABOVE THE SIDEWALK SHALL NOT EXTEND INTO OR OCCUPY MORE
 THAN TWO-THIRDS THE WIDTH OF THE SIDEWALK MEASURED FROM
 THE BUILDING. STANCHIONS OR COLUMNS THAT SUPPORT
 AWNINGS , CANOPIES, MARQUEES AND SIGNS SHALL BE LOCATED
 NOT LESS THAN 2 FEET (610 MM) IN FROM THE CURB LINE.
  
 15) SHEET A7.01 THE DETAIL# 3 INDICATES A NEW ENTRY
 AREAS WITH A SECTION THROUGH HOW THIS AREAIS TO BE
 BUILT. THE WALL AREA REMOVED DOES HOWEVER LEAVE 3
 COURSES OF BLOCK IN THE AIR WITH A NOTE SEE STRUCTURAL
 FOR REINFORCEMENT. THE STRUCTURAL SHEET S2.01 HOWEVER
 DOES NOT DETAIL ANY WORK ON THE BUILDING NOT FACING
 DIXIE HWY. ADDITIONAL INFORMATION REQUIRED 106.1.2.
  
 16)SHEET A7.01 THE DETAIL# 4 INDICATES A NEW ENTRY
 AREAS WITH A SECTION THROUGH HOW THIS AREAIS TO BE
 BUILT. THE WALL AREA REMOVED DOES HOWEVER LEAVE 3
 COURSES OF BLOCK IN THE AIR WITH A NOTE SEE STRUCTURAL
 FOR REINFORCEMENT. THE STRUCTURAL SHEET S2.01 HOWEVER
 DOES NOT DETAIL ANY WORK ON THE BUILDING NOT FACING
 DIXIE HWY. ADDITIONAL INFORMATION REQUIRED 106.1.2.
  
 17) ) 1609.1.4 PROTECTION OF OPENINGS. IN WIND-BORNE
 DEBRIS REGIONS, EXTERIOR GLAZING THAT RECEIVES POSITIVE
 PRESSURE IN THE LOWER 60 FEET (18.3 M) IN BUILDINGS
 SHALL BE ASSUMED TO BE OPENINGS AND THE BALANCE OF
 GLAZED OPENINGS IN THE REST OF THE BUILDING SHALL BE
 ASSUMED TO BE ZERO UNLESS SUCH GLAZING THAT RECEIVES
 POSITIVE PRESSURE IS IMPACT RESISTANT OR PROTECTED WITH
 AN IMPACT RESISTANT COVERING MEETING THE REQUIREMENTS
 OF SSTD 12, ASTM E 1886 AND ASTM E 1996, OR MIAMI-DADE
 TAS 201, 202 AND 203 REFERENCED THEREIN AS FOLLOWS: 1.
 GLAZED OPENINGS LOCATED WITHIN 30 FEET (9.1 M) OF GRADE
 SHALL MEET THE REQUIREMENTS OF THE LARGE MISSILE TEST.
 2.GLAZED OPENINGS LOCATED MORE THAN 30 FEET (9.1
 M) ABOVE GRADE SHALL MEET THE PROVISIONS OF THE SMALL
 MISSILE TEST.
  
  
 18)PRODUCT APPROVALS SUBMITTED WITH PERMIT
 APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA PRODUCT
 APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH STATEWIDE
 APPROVAL ARE REQUIRED TO BE SUBMITTED WITH A COVER
 SHEET THAT LISTS THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE STATEWIDE APPROVAL,
 SUBMIT AN APPLICATION FOR LOCAL PRODUCT APPROVAL OR
 SITE SPECIFIC FORM PER RULE 9B-72.
  
 19)FL BLD CODE 1609.1.4: COMPONENTS & CLADDING,
 PROVIDE 2 COPIES(3 IF THRESHOLD OR RESIDENT INSPECTOR)
 OF PRODUCT TESTING REPORTS ,MISSING REPORTS ARE AS
 FOLLOWS:
 A) STOREFRONT WINDOWS- NO REPORT SUBMITTED
 B) GLAZED DOORS- NO REPORT SUBMITTED
 C) MULLIONS HORIZONTAL OR VERTICAL
 D) LINTELS NO REPORT SUBMITTED
 E) EXTERIOR METAL HOLLOW CORE DOORS NO REPORT
 SUBMITTED
 F) ROOFING ASSEMBLIES SEE NOTE BELOW
 G) STORM SHUTTERS SEE NOTES BLOW
  
 19) ROOFING REPORT:THIS ROOF IS MISSING OR NOT IN
 COMPLIANCE WITH THE FOLLOW ITEMS:
  
 XX___ CONTRACTOR DID NOT PROVIDE THE MEANROOF
 HEIGHT.
  
 XX___ CONTRACTOR DID NOT INDICATE THE ROOF PITCH.
  
 XX___ CONTRACTOR FAILED TO INDICATE WHICH SYSTEM TO BE
 USED.
  
 XX___ THE SYSTEM PROVIDED HAS A LOWPRESSURE FOR
 ZONE _2& 3__ .
  
 POSSIBLY___ THE SYSTEM PROVIDED STATESLIMITATION#
 7, SHOULD THE FASTENERRESISTANCE BE LESS THAN THAT
 REQUIRED, AS DETERMINED BY THEBUILDING OFFICIAL, A
 REVISEDFASTENER SPACING, PREPARED , SIGNEDAND
 SEALED BY A FLORIDA REGISTERED PROFESSIONAL ENGINEER,
 REGISTERED ARCHITECT OR REGISTERED ROOF CONSULTANT MAY
 BE SUBMITTED.
  
 POSSIBLY___THE SYSTEM PROVIDED INDICATESLIMITATION#
 9, NO ENHANCED FASTENING ALLOWED.
  
 20) HURRICANE MANUFACTURING CORP. SERIES HMC 1000 AL
 STOREFRONT SYSTEM REQUIRES A FLORIDA COVERSHEET AND
 ASSOCIATED REPORT BY ENGCO INC # 05-228.
  
 21) SHEETA3.02DETAIL# 5 IS THE WALL ADJACENT TO THE
 BRAILLE CLUB OF THE PALM BEACHES, THIS APPEARS TO BE A
 ZERO LOT LINE WALL REQUIRING A 3 HR FIRE RATING. AS
 DISCUSSED EARLIER UNDER COMMENT#12A THERE CAN BE NO
 OPENINGS ON THIS WALL, PLEASE LOOK AT SECTION 602.3
  
 TYPE III BUILDINGS: 602.3 TYPE III.
 TYPE III CONSTRUCTION IS THAT TYPE OF CONSTRUCTION IN
 WHICH THE EXTERIOR WALLS ARE OF NONCOMBUSTIBLE
 MATERIALS AND THE INTERIOR BUILDING ELEMENTS ARE OF ANY
 MATERIAL PERMITTED BY THIS CODE. FIRE-RETARDANT-TREATED
 WOOD FRAMING COMPLYING WITH SECTION 2303.2 SHALL BE
 PERMITTED WITHIN EXTERIOR WALL ASSEMBLIES OF A 2-HOUR
 RATING OR LESS.
 THIS PARTICULAR WALL AND PARAPET WILL REQUIRE A 3 HOUR
 FIRE RATING!!! PLEASE REVISE DETAILS.
  
 22) THE STRUCTURAL SHEETS DO NOT INDICATE AS TO WHAT
 CODE OR TO WHAT WIND DESIGN THEY DESIGNED THIS BUILDING
 TOO?
  
 2004 FL. BLD CODE 1603.1.4 THE
 FOLLOWING INFORMATION RELATED TO WIND
 SHALL BE SHOWN ON THE CONSTRUCTION
 DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
  
 23) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 BUILDING PLAN REVIEW II
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]