| 2007-11-15 07:17:26 | |
| | |
| | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: |
| | |
| | THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004 |
| | RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002, |
| | NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND |
| | NONCOMPLIANT WITH THE FOLLOWING: |
| | |
| | THESE COMMENTS ARE THE SAME AS THE PREVIOUS REVIEW . AN |
| | ELECTRICAL PERMIT WAS APPLIED FOR UNDER THE |
| | OWNER/BUILDER STATUTE 489, THEREFORE THE NOTE ON SHEET |
| | A-2 REGARDING THE "CONTRACTOR SHALL SUBMIT ELECTRICAL |
| | LAYOUT" IS IRRELEVANT. COMMENTS MUST BE ADDRESSED. SEE |
| | FS 553.80(2)(B) ATTACHED WITH COMMENT SHEET. |
| | |
| | 1} BATH CIRCUIT REQUIRED TO HAVE A 20 AMP RECEPTACLE |
| | PER 210.11(C) (3), LOCATED PER 210.52(D), AND BE GFI |
| | PROTECTED PER 210.8(A) (1). THE ONE ON THE PLAN DOES |
| | NOT COMPLY WITH 210.52(D) FOR SPACING REQUIREMENTS. |
| | ALSO PLEASE NOTE 210.(C)(3) COMPLIANCE ON THE PLAN. |
| | |
| | 2} R313.1.1 SMOKE ALARMS SHALL BE LOCATED AS REQUIRED |
| | IN NEW DWELLINGS WHEN REPAIRS OR ADDITIONS REQUIRING A |
| | PERMIT OCCUR. SEE ARTICLE FOR COMPLETE TEXT. SHOW |
| | LOCATION ON PLANS. |
| | |
| | 3} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST |
| | PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.3. FBC. |
| | IF AN ARCHITECT OR ENGINEER, COMPLY WITH 418 AND 417 |
| | FS, RESPECTIVELY. THE ENGINEER THAT SEALED THE |
| | ELECTRICAL PLAN STATES RESPONSIBILITY FOR STUCTURAL |
| | ONLY AND THEREFORE NO ONE HAS TAKEN RESPONSIBILITY FOR |
| | THE ELECTRICAL PLAN. |
| | |
| | 4} THE LUMINAIRE SHOWN OVER THE TUB MUST COMPLY WITH |
| | 410.4(D). |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |