Plan Review Notes
Plan Review Notes For Permit 07070201
Permit Number 07070201
Review Stop E
Sequence Number 2
Notes
Date Text
2007-11-15 07:17:26 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING:
  
 THESE COMMENTS ARE THE SAME AS THE PREVIOUS REVIEW . AN
 ELECTRICAL PERMIT WAS APPLIED FOR UNDER THE
 OWNER/BUILDER STATUTE 489, THEREFORE THE NOTE ON SHEET
 A-2 REGARDING THE "CONTRACTOR SHALL SUBMIT ELECTRICAL
 LAYOUT" IS IRRELEVANT. COMMENTS MUST BE ADDRESSED. SEE
 FS 553.80(2)(B) ATTACHED WITH COMMENT SHEET.
  
 1} BATH CIRCUIT REQUIRED TO HAVE A 20 AMP RECEPTACLE
 PER 210.11(C) (3), LOCATED PER 210.52(D), AND BE GFI
 PROTECTED PER 210.8(A) (1). THE ONE ON THE PLAN DOES
 NOT COMPLY WITH 210.52(D) FOR SPACING REQUIREMENTS.
 ALSO PLEASE NOTE 210.(C)(3) COMPLIANCE ON THE PLAN.
  
 2} R313.1.1 SMOKE ALARMS SHALL BE LOCATED AS REQUIRED
 IN NEW DWELLINGS WHEN REPAIRS OR ADDITIONS REQUIRING A
 PERMIT OCCUR. SEE ARTICLE FOR COMPLETE TEXT. SHOW
 LOCATION ON PLANS.
  
 3} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST
 PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.3. FBC.
 IF AN ARCHITECT OR ENGINEER, COMPLY WITH 418 AND 417
 FS, RESPECTIVELY. THE ENGINEER THAT SEALED THE
 ELECTRICAL PLAN STATES RESPONSIBILITY FOR STUCTURAL
 ONLY AND THEREFORE NO ONE HAS TAKEN RESPONSIBILITY FOR
 THE ELECTRICAL PLAN.
  
 4} THE LUMINAIRE SHOWN OVER THE TUB MUST COMPLY WITH
 410.4(D).
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]