| 2007-12-03 16:32:29 | 2004 FBC W/2007 REVISIONS |
| | ADDITION |
| | |
| | DENIED BY BUILDING |
| | |
| | 1) SUBMIT 2 COPIES OF THE ENERGY CALC. FORMS THAT HAVE |
| | BEEN SIGNED BY THE OWNER/AGENT. SEE FBC CHAPTER 13. |
| | |
| | 2) REVISE THE INTERNAL WALL DETAIL AND THE INSULATION |
| | SCHEDULE ON SHEET A-2, WHICH SPECIFY R-19 INSULATION IN |
| | THE CEILING AND R-4.1 ON THE MASONRY WALLS. THE ENERGY |
| | CALC. FORM SUBMITTED REQUIRES A MINIMUM OF R-30 IN THE |
| | CEILING AND R-5 ON THE MASONRY WALLS. SEE FBC |
| | 13-600.1.C. |
| | |
| | 3) SPECIFY THE CONNECTORS/HANGERS THAT WILL BE USED TO |
| | ATTACH THE 2 X 10 RAFTERS TO THE LEDGER AT THE COVERED |
| | PORCH. |
| | |
| | 4) ON SHEET A4 THE STEEL BUCKET DETAIL SPECIFIES 2- 2 X |
| | 12P.T. AND THE FRAMING PLAN SHOWS 2- 2 X 10 . PLEASE |
| | CLARIFY. |
| | |
| | 5) IN ADDITION TO THE FLORIDA COVERSHEET THAT WAS |
| | SUBMITTED FOR THE GLASS BLOCK, SUBMIT 2 COPIES OF |
| | INSTALLATION INSTRUCTIONS AND EVALUATION REPORTS AS |
| | REQUIRED BY FAC RULE 9B-72. |
| | |
| | 6) ON THE NOA FOR THE ALTUSA "S" CLAY ROOF TILE SPECIFY |
| | THE FASTENING SYSTEM THAT WILL BE USED. CIRCLE THE ITEM |
| | WITH THE APPROPRIATE ATTACHMENT RESISTANCE ON THE NOA. |
| | FBC 106.1.2 |
| | |
| | 7) SUBMIT PRODUCT APPROVALS FOR THE STORM PANELS |
| | REQUIRED FOR ALL GLAZED OPENINGS THAT ARE NOT LARGE |
| | MISSLE IMPACT RESISTANT. SPECIFY THE MOUNT TYPE, |
| | ANCHORS, ANCHOR SPACING, SPANS, ETC. ON THE PRODUCT |
| | APPROVAL/NOA. SEE FBC R301.2.1.2. |
| | |