Plan Review Notes
Plan Review Notes For Permit 07070201
Permit Number 07070201
Review Stop B
Sequence Number 2
Notes
Date Text
2007-12-03 16:32:292004 FBC W/2007 REVISIONS
 ADDITION
  
 DENIED BY BUILDING
  
 1) SUBMIT 2 COPIES OF THE ENERGY CALC. FORMS THAT HAVE
 BEEN SIGNED BY THE OWNER/AGENT. SEE FBC CHAPTER 13.
  
 2) REVISE THE INTERNAL WALL DETAIL AND THE INSULATION
 SCHEDULE ON SHEET A-2, WHICH SPECIFY R-19 INSULATION IN
 THE CEILING AND R-4.1 ON THE MASONRY WALLS. THE ENERGY
 CALC. FORM SUBMITTED REQUIRES A MINIMUM OF R-30 IN THE
 CEILING AND R-5 ON THE MASONRY WALLS. SEE FBC
 13-600.1.C.
  
 3) SPECIFY THE CONNECTORS/HANGERS THAT WILL BE USED TO
 ATTACH THE 2 X 10 RAFTERS TO THE LEDGER AT THE COVERED
 PORCH.
  
 4) ON SHEET A4 THE STEEL BUCKET DETAIL SPECIFIES 2- 2 X
 12P.T. AND THE FRAMING PLAN SHOWS 2- 2 X 10 . PLEASE
 CLARIFY.
  
 5) IN ADDITION TO THE FLORIDA COVERSHEET THAT WAS
 SUBMITTED FOR THE GLASS BLOCK, SUBMIT 2 COPIES OF
 INSTALLATION INSTRUCTIONS AND EVALUATION REPORTS AS
 REQUIRED BY FAC RULE 9B-72.
  
 6) ON THE NOA FOR THE ALTUSA "S" CLAY ROOF TILE SPECIFY
 THE FASTENING SYSTEM THAT WILL BE USED. CIRCLE THE ITEM
 WITH THE APPROPRIATE ATTACHMENT RESISTANCE ON THE NOA.
 FBC 106.1.2
  
 7) SUBMIT PRODUCT APPROVALS FOR THE STORM PANELS
 REQUIRED FOR ALL GLAZED OPENINGS THAT ARE NOT LARGE
 MISSLE IMPACT RESISTANT. SPECIFY THE MOUNT TYPE,
 ANCHORS, ANCHOR SPACING, SPANS, ETC. ON THE PRODUCT
 APPROVAL/NOA. SEE FBC R301.2.1.2.
  