| Plan Review Notes For Permit 07070201 |
| Permit Number |
07070201 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-07-13 09:22:36 | | | | | | | | | | NONCOMPLIANT | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE | | | COMPLIANCE AND RESUBMIT FOR REVIEW. | | | | | | 1} BATH CIRCUIT REQUIRED TO HAVE A 20 AMP RECEPTACLE | | | PER 210.11(C) (3), LOCATED PER 210.52(D), AND BE GFI | | | PROTECTED PER 210.8(A) (1). THE ONE ON THE PLAN DOES | | | NOT COMPLY WITH 210.52(D) FOR SPACING REQUIREMENTS. | | | ALSO PLEASE NOTE 210.(C)(3) COMPLIANCE ON THE PLAN. | | | | | | 2} R313.1.1 SMOKE ALARMS SHALL BE LOCATED AS REQUIRED | | | IN NEW DWELLINGS WHEN REPAIRS OR ADDITIONS REQUIRING A | | | PERMIT OCCUR. SEE ARTICLE FOR COMPLETE TEXT. SHOW | | | LOCATION ON PLANS. | | | | | | 3} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST | | | PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.3. FBC. | | | IF AN ARCHITECT OR ENGINEER, COMPLY WITH 418 AND 417 | | | FS, RESPECTIVELY. THE ENGINEER THAT SEALED THE | | | ELECTRICAL PLAN STATES RESPONSIBILITY FOR STUCTURAL | | | ONLY AND THEREFORE NO ONE HAS TAKEN RESPONSIBILITY FOR | | | THE ELECTRICAL PLAN. | | | | | | 4} THE LUMINAIRE SHOWN OVER THE TUB MUST COMPLY WITH | | | 410.4(D). | | | | | | 5} THE REFERENCE TO THE "SBC" IN THE KEYED NOTES, ALL | | | SHEETS, DOES NOT APPLY AS THAT CODE IS NO LONGER USED. | | | REMOVE FROM PLANS TO AVOID CONFUSION IN THE FIELD. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | | [email protected] |
|