Plan Review Notes
Plan Review Notes For Permit 07070201
Permit Number 07070201
Review Stop E
Sequence Number 1
Notes
Date Text
2007-07-13 09:22:36 
  
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} BATH CIRCUIT REQUIRED TO HAVE A 20 AMP RECEPTACLE
 PER 210.11(C) (3), LOCATED PER 210.52(D), AND BE GFI
 PROTECTED PER 210.8(A) (1). THE ONE ON THE PLAN DOES
 NOT COMPLY WITH 210.52(D) FOR SPACING REQUIREMENTS.
 ALSO PLEASE NOTE 210.(C)(3) COMPLIANCE ON THE PLAN.
  
 2} R313.1.1 SMOKE ALARMS SHALL BE LOCATED AS REQUIRED
 IN NEW DWELLINGS WHEN REPAIRS OR ADDITIONS REQUIRING A
 PERMIT OCCUR. SEE ARTICLE FOR COMPLETE TEXT. SHOW
 LOCATION ON PLANS.
  
 3} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST
 PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.3. FBC.
 IF AN ARCHITECT OR ENGINEER, COMPLY WITH 418 AND 417
 FS, RESPECTIVELY. THE ENGINEER THAT SEALED THE
 ELECTRICAL PLAN STATES RESPONSIBILITY FOR STUCTURAL
 ONLY AND THEREFORE NO ONE HAS TAKEN RESPONSIBILITY FOR
 THE ELECTRICAL PLAN.
  
 4} THE LUMINAIRE SHOWN OVER THE TUB MUST COMPLY WITH
 410.4(D).
  
 5} THE REFERENCE TO THE "SBC" IN THE KEYED NOTES, ALL
 SHEETS, DOES NOT APPLY AS THAT CODE IS NO LONGER USED.
 REMOVE FROM PLANS TO AVOID CONFUSION IN THE FIELD.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]