| 2007-07-19 18:39:39 | DENIED BY BUILDING |
| | |
| | 1) SUBMIT A SURVEY/SITE PLAN INDICATING THE LOCATION OF |
| | THE ADDITION AND THE DISTANCES TO PROPERTY LINES. |
| | |
| | 2)) FBC* 1804.2.2AREA OF QUESTIONABLE |
| | SOIL.SUBMIT A GEOTECHNICAL REPORT |
| | TO VERIFY THE SAFE BEARING CAPACITY OF |
| | THE SOIL. |
| | |
| | 3) SUBMIT ENERGY CALCULATIONS AS REQUIRED BY FBC |
| | CHAPTER 13. |
| | |
| | 4) THE DESIGN INFORMATION ON ALL OF THE SHEETS |
| | INCORRECTLY SPECIFY SBC INSTEAD OF FBC 2004. |
| | |
| | 5) IN THE ROOF NOTES ON A5, FBC 2001 IS INCORRECTLY |
| | SPECIFIED INSTEAD OF FBC 2004. |
| | |
| | 6) ON A3 THE FOUNDATION NOTES NEED TO BE UPDATED TO |
| | SPECIFY ACI 530-02 AND 630-02. WHICH ARE THE EDITIONS |
| | REFERENCE IN THE 2004 FBC. |
| | |
| | 7) THE GLASS BLOCK NOTES ON SHEET A2 INCORRECTLY |
| | SPECIFY SFBC . SEE FBC 2110. |
| | |
| | 8)R322.1 REQUIRES AT LEAST ONE BATHROOM WITH A DOOR |
| | THAT HAS A 29" CLEAR OPENING MEASURED BETWEEN THE FACE |
| | OF THE DOOR AND THE OPPOSITE STOP WITH THE DOOR OPEN 90 |
| | DEGREES. |
| | |
| | 9) SHOW COMPLIANCE WITH R807.1 ATTIC ACCESS. |
| | IN BUILDINGS WITH COMBUSTIBLE CEILING OR ROOF |
| | CONSTRUCTION, AN ATTIC ACCESS OPENING SHALL BE PROVIDED |
| | TO ATTIC AREAS THAT EXCEED 30 SQUARE FEET (2.8 M 2 ) |
| | AND HAVE A VERTICAL HEIGHT OF 30 INCHES (762 MM) OR |
| | GREATER. |
| | THE ROUGH-FRAMED OPENING SHALL NOT BE LESS THAN 22 |
| | INCHES BY 30 INCHES (559 MM BY 762 MM) AND SHALL BE |
| | LOCATED IN A HALLWAY OR OTHER READILY ACCESSIBLE |
| | LOCATION. A 30-INCH (762 MM) MINIMUM UNOBSTRUCTED |
| | HEADROOM IN THE ATTIC SPACE SHALL BE PROVIDED AT SOME |
| | POINT ABOVE THE ACCESS OPENING. SEE SECTION M1305.1.3 |
| | FOR ACCESS REQUIREMENTS WHERE MECHANICAL EQUIPMENT IS |
| | LOCATED IN ATTICS. |
| | |
| | 10) SPECIFY THE CEILING FINISH THAT WILL BE USED AT THE |
| | COVERED PORCH. |
| | |
| | 11) SUBMIT SIGNED AND SEALED GRAVITY LOAD CALCULATIONS |
| | FOR THE DOUBLE 2 X 10 BEAM CARRYING THE COVERED PORCH |
| | CEILING/RAFTERS. |
| | |
| | 12) SPECIFY THE LENGTH/EMBED DEPTH OF THE 5/8" DIAMETER |
| | ANCHORS FOR THE COVERED PORCH LEDGER. |
| | |
| | 13) SPECIFY THE CONNECTORS/HANGERS THAT WILL BE USED TO |
| | ATTACH THE 2 X 10 RAFTERS TO THE COVERED PORCH LEDGER. |
| | |
| | 14)REVISE THE ROOF SHEATHING FASTENING SPECIFICATIONS |
| | TO COMPLY WITH FBC R803.2.3.1 WHICH REQURES 8D RING |
| | SHANK NAILS IN ALL ROOF ZONES. |
| | |
| | 15)PRODUCT APPROVALS SUBMITTED WITH |
| | PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| | ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| | PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| | PLEASE SEE THE STATE WEBSITE AT |
| | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| | STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET THAT LISTS |
| | THE PRODUCT IDENTITY NUMBER FROM THE |
| | STATE. |
| | |
| | 16)WPB ADMIN CODE 106.3* PRODUCT |
| | APPROVALS. THOSE PRODUCT WHICH ARE |
| | REGULATED BY DCA RULE 9B-72 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL |
| | FOR JURISDICTIONAL APPROVAL. |
| | |
| | 17) SUBMIT 2 COPIES OF PRODUCT APPROVALS FOR THE GLASS |
| | BLOCK. |
| | |
| | 18) THE NOA FOR THE ALTUSA "S" CLAY ROOF TILE HAS BEEN |
| | SUPERSEDED BY NOA NO. 05-0901.06. PLEASE SUBMIT THE |
| | CURRENT NOA. THIS PRODUCT DOES NOT HAVE A STATE PRODUCT |
| | APPROVAL. HOWEVER, A CURRENT MIAMI-DADE NOA IS |
| | ACCEPTABLE. |
| | |
| | 19)A FLORIDA COVERSHEET WAS SUBMITTED FOR MONIER ROOF |
| | TILE WITHOUT THE INSTALLATION INSTRUCTIONS OR |
| | EVALUATION REPORT. PLEASE CLARIFY. ONLY SUBMIT THE |
| | PRODUCT APPROVAL FOR THE ROOF TILE THAT WILL BE |
| | INSTALLED. |
| | |
| | 20) THE NOA FOR THE TRACO SINGLE HUNG WINDOWS HAS BEEN |
| | REVISED BY NOA NO. 05-0930.03. SUBMIT THE NEW NOA. |
| | |
| | 21) THE VALUE OF THE PROJECT HAS BEEN INCREASED TO |
| | $29312.00. ADDITIONAL FEES ARE DUE. |
| | |
| | 22) IF THE SHEETS THAT HAVE THE COUNTY IMPACT FEE STAMP |
| | ARE REVISED, RETURN THEM WITH THE RESUBMITTED PLANS OR |
| | THE NEW PLANS WILL HAVE TO BE RESTAMPED BY THE COUNTY. |
| | |
| | - ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)805-6714 |
| | |
| | |
| | |
| | |