| 2007-08-09 08:31:20 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & |
| | REFERENCED CODES WITH 2005, 2006 REVISIONS, AND CHAPTER |
| | 1 CITY OF WEST PALM BEACH AMENDMENTS. |
| | |
| | *** DENIED *** |
| | 1) MECHANICAL PLANS SUBMITTED GRAYED OUT AREAS AND |
| | OTHER DARKEN LINES THAT MAKE IT DIFFICULT TO SEE ALL |
| | MECHANICAL DETAIL ON THE PLAN THEIR FOR SOME ITEMS MAY |
| | BE MISSED ON THIS PLAN REVIEW. CONSTRUCTION DOCUMENTS |
| | SHALL BE OF SUFFICIENT CLARITY. PER 2004 FBC 106.1.1. |
| | PLEASE CORRECT. |
| | |
| | 2) MECHANICAL PLANS (EQUIPMENT INFORMATION) LISTS TWO |
| | A/C SYSTEMS AS #1, PLEASE CORRECT. |
| | |
| | 3) AS NOTED IN LAST REVIEW 7-16-07 NOTE #6, PLEASE SHOW |
| | ON MECHANICAL PLANS COMBUSTION AIR CALCULATIONS FOR GAS |
| | CLOTHES DRYER IN LAUNDRY ROOM AND PROVIDE COMBUSTION |
| | AIR AND MAKE-UP AIR IF REQUIRED, SEE 2004 FBC/R G2407.1 |
| | (304.1). |
| | |
| | 4) SHOW ON MECHANICAL PLAN THE CLOTHES DRYER VENT AND |
| | STATE WERE IT WILL VENT TO, SEE 2004 FBC/R R303.4.2. |
| | |
| | 5) SHOW ON MECHANICAL PLAN THE CFM'S. AT ALL BATHROOM |
| | EXHAUST FANS, SEE 2004 FBC/R R303.3. |
| | |
| | 6) THE ELECTRICAL PLAN SHOWS A BATHROOM EXHAUST FAN IN |
| | THE MASTER BATH NEAR THE TUB, AS THE WINDOWS APPEAR TO |
| | BE FIXED AT THAT LOCATION SEE 2004 FBC/R R303.3 AND |
| | PLEASE CORRECT PLANS SO THEY COINCIDE. |
| | |
| | 7) SEE YELLOW HIGH LIGHTS ON MECHANICAL PLAN SHOWING |
| | A/C DUCTS THAT NEED TO BE SIZED. |
| | |
| | 8) MECHANICAL PLAN DOES NOT SHOW WHICH AIR HANDLER AND |
| | CONDENSER UNIT IS #1, PLEASE CORRECT. |
| | |
| | 9) PLEASE ADD A SECOND COPY OF THE INSTALLATION |
| | INSTRUCTIONS FOR THE UNVENTED GAS LOG HEATER, AS ONLY |
| | ONE WAS SUBMITTED. |
| | |
| | MECHANICAL PLAN REVIEW BY; |
| | TOM GORDON (561) 805-6729 |
| | E-MAIL: [email protected]. |