Plan Review Notes
Plan Review Notes For Permit 07070169
Permit Number 07070169
Review Stop E
Sequence Number 2
Notes
Date Text
2007-08-08 08:07:23 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002, 2004
 FBC AS AMENDED, CHAPTER 1.AND FOUND NONCOMPLIANT WITH
 THE FOLLOWING:
  
 1} A SMOKE ALARM MUST BE INSTALLED OUTSIDE BEDROOM #4
 TO COMPLY WITH THE REQUIREMENT "OUTSIDE EACH SEPARATE
 SLEEPING AREA IN THE IMMEDIATE VICINITY OF THE
 BEDROOMS." R313.1.1 FBC, 2004 REVISED 2006.
  
 ALSO SEE THE DEFINITION OF "SMOKE DETECTORS" 11.8.2.1
 NFPA-72, CLARIFY IF USING DETECTORS OR ALARMS, TO AVOID
 CONFUSION IN THE FIELD. IF USING DETECTORS INDICATE THE
 LOCATIONS OF THE SOUNDING DEVICES.
  
 2} THE DISCONNECTS FOR CONDENSERS #1 & #2 DO NOT MEET
 THE CLEARANCE REQUIREMENTS OF 110.26, 2005 NEC.
  
 3} PANEL "A", CIRCUIT #10, #12 CONDUCTOR ON A60 AMP
 CIRCUIT BREAKER IS IN VIOLATION OF 310.16 NEC.
  
 4} PANEL "A", CIRCUIT #16, #14 CONDUCTOR ON 20 AMP
 CIRCUIT BREAKER, VIOLATION OF 310.16 NEC.
  
 THE FOLLOWING , ALTHOUGH NOT VIOLATIONS WILL NEED TO BE
 REVISED IF NOT ACTUALLY INTENDED TO BE INSTALLED: PANEL
 "A"CIRCUITS 9 & 11, #10 CONDUCTORS, 20 AMP BREAKERS.
 PANEL "B", CIRCUIT #6, #6 CONDUCTOR, WHICH WON'T
 PHYSICALLY FIT, ON A 20 AMP BREAKER. CIRCUIT #10, #10
 WIRE ON A 20 AMP BREAKER, CIRCUIT #'S 18, 23, 25, 26 &
 29 ALL HAVE #12 CONDUCTORS ON15 AMP CIRCUIT BREAKERS.
 CIRCUIT #5 IS LISTED AS A #6 CONDUCTOR ON A 20 AMP
 BREAKER, CIRCUIT #9, #10 WIRE, 20 AMP BREAKER, CIRCUIT
 #13, #8 WIRE, 20 AMP BREAKER, CIRCUIT #17, #10 WIRE,
 20AMP BREAKER. THESE ITEMS NEED TO BE CLARIFIED BY THE
 DESIGNER OF RECORD TO VERIFY HIS DESIGN INTENTIONS
 PRIOR TO BEING INCORRECTLY INSTALLED IN THE FIELD.
  
 NOTE:
 THE GFI RECEPTACLES PLACED IN THE ISLAND BETWEEN THE
 FAMILY ROOM AND THE KITCHEN MAY NOT BE IN COMPLIANCE
 WITH 210.52(C)(5) IF UNDER THE OVERHANGING COUNTERTOP
 THAT EXTENDS 6" OR MORE, SEE THE EXCEPTION, THAT
 ARTICLE.
  
 PLEASE MAKE THE CORRECTIONS NEEDED FOR CODE COMPLIANCE
 AND TO SHOW DESIGN INTENTION, AND RESUBMIT FOR REVIEW.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  