| Plan Review Notes For Permit 07070169 |
| Permit Number |
07070169 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2007-08-11 12:31:08 | | | | | | | DENIED | | | | | | 1)PROVIDE THE CORRECT INSULATION R- VALUES ON THE | | | DRAWINGS TO MATCH THE CREDITS TAKEN ON THE ENERGY | | | CALC'S R-30 CEILING, R-11 FRAMED WALL BETWEEN | | | CONDITIONED AND UNCONDITIONED SPACES, ETC. | | | | | | 2)THE 1X HEAVY MULLION PRODUCT APPROVAL WILL NOT MEET | | | THE PRESSURE REQUIREMENTS FOR THE LARGE LIVINGROOM | | | WINDOW. THE 2X6 MULLION UNDER THE SAME FL# IN 2X HEAVY | | | WALL WILL MEET YOUR PRESSURES FOR AN 8'-0" TRIBUTARY | | | WIDTH AND 12'-0" OPENING HEIGHT. | | | | | | BLDG PLAN REVIEW | | | ADRIAN MORSE | | | 561-805-6716 |
|