Plan Review Notes
Plan Review Notes For Permit 07070169
Permit Number 07070169
Review Stop B
Sequence Number 2
Notes
Date Text
2007-08-11 12:31:08 
  
 DENIED
  
 1)PROVIDE THE CORRECT INSULATION R- VALUES ON THE
 DRAWINGS TO MATCH THE CREDITS TAKEN ON THE ENERGY
 CALC'S R-30 CEILING, R-11 FRAMED WALL BETWEEN
 CONDITIONED AND UNCONDITIONED SPACES, ETC.
  
 2)THE 1X HEAVY MULLION PRODUCT APPROVAL WILL NOT MEET
 THE PRESSURE REQUIREMENTS FOR THE LARGE LIVINGROOM
 WINDOW. THE 2X6 MULLION UNDER THE SAME FL# IN 2X HEAVY
 WALL WILL MEET YOUR PRESSURES FOR AN 8'-0" TRIBUTARY
 WIDTH AND 12'-0" OPENING HEIGHT.
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716