| Plan Review Notes For Permit 07070169 |
| Permit Number |
07070169 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-07-16 09:23:39 | *** DENIED *** | | | 1) PLEASE STATE ON PLANS THE BUILDING CODE BEING USED | | | FOR THIS PROJECT, PRESENTLY 2004 FBC W/ 2006 REVISIONS, | | | SEE 2004 FBC 106.1.1. | | | | | | 2) PLEASE SHOW THE JOB ADDRESS IN THE TITLE BLOCK, SEE | | | 2004 FBC 106.1.1. | | | | | | 3) PLEASE SUBMIT MECHANICAL (A/C) PLANS FOR REVIEW, SEE | | | 2004 FBC CITY WPB AMEND. 106.3.5.4 (10). | | | | | | 4) PLEASE SUBMIT ENERGY CALCULATIONS, SEE 2004 FBC | | | 13-101.2.1. | | | | | | 5) PLEASE SUBMIT COOLING LOAD CALCULATIONS, SEE 2004 | | | FBC 13-607.1.ABC.1. | | | | | | 6) SHOW ON MECHANICAL PLAN COMBUSTION AIR CALCULATION | | | FOR GAS VENT FREE FIREPLACE IN CLUB ROOM, AND GAS | | | CLOTHES DRYER IN LAUNDRY ROOM. PROVIDE COMBUSTION AND | | | MAKE-UP AIR IF REQUIRED, SEE 2004 FBC/R G2407.1 | | | (304.1). | | | | | | 7) ELECTRICAL PLANS PANEL LISTS 4 A/C SYSTEMS BUT PLANS | | | ONLY SHOW 3 A/C SYSTEMS, PLEASE CORRECT. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|