Plan Review Notes
Plan Review Notes For Permit 07070169
Permit Number 07070169
Review Stop M
Sequence Number 1
Notes
Date Text
2007-07-16 09:23:39*** DENIED ***
 1) PLEASE STATE ON PLANS THE BUILDING CODE BEING USED
 FOR THIS PROJECT, PRESENTLY 2004 FBC W/ 2006 REVISIONS,
 SEE 2004 FBC 106.1.1.
  
 2) PLEASE SHOW THE JOB ADDRESS IN THE TITLE BLOCK, SEE
 2004 FBC 106.1.1.
  
 3) PLEASE SUBMIT MECHANICAL (A/C) PLANS FOR REVIEW, SEE
 2004 FBC CITY WPB AMEND. 106.3.5.4 (10).
  
 4) PLEASE SUBMIT ENERGY CALCULATIONS, SEE 2004 FBC
 13-101.2.1.
  
 5) PLEASE SUBMIT COOLING LOAD CALCULATIONS, SEE 2004
 FBC 13-607.1.ABC.1.
  
 6) SHOW ON MECHANICAL PLAN COMBUSTION AIR CALCULATION
 FOR GAS VENT FREE FIREPLACE IN CLUB ROOM, AND GAS
 CLOTHES DRYER IN LAUNDRY ROOM. PROVIDE COMBUSTION AND
 MAKE-UP AIR IF REQUIRED, SEE 2004 FBC/R G2407.1
 (304.1).
  
 7) ELECTRICAL PLANS PANEL LISTS 4 A/C SYSTEMS BUT PLANS
 ONLY SHOW 3 A/C SYSTEMS, PLEASE CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.