| Date |
Text |
| 2007-07-13 15:49:27 | |
| | |
| | |
| | NONCOMPLIANT |
| | |
| | PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE |
| | COMPLIANCE AND RESUBMIT FOR REVIEW. |
| | |
| | 1} THE ELECTRICAL RISER INDICATES 150 AMP MAIN BREAKERS |
| | IN THE DISCONNECTS AND 150 AMP PANELS. THE LOAD |
| | CALCULATIONS FOR EACH PANEL EXCEEDS THAT AMPERAGE. |
| | 220.40 NEC. ALSO THE RATING FOR THE PANELS SCHEDULES AT |
| | 200 AMP, DO NOT CORRELATE WITH THE RISER. PROVIDE LOAD |
| | CALCULATIONS PER 220 SECTION I, STANDARD CALCULATION, |
| | IF DERATING THE NEUTRAL, OR 220.SECTION III, OPTIONAL |
| | CALCULATIONS. |
| | |
| | 2} THERE ARE FEEDS TO THE POOL HEATER, PUMP AND LIGHTS |
| | FROM PANEL "B", THE RISER FEEDS A 60 AMP POOL PANEL |
| | FROM PANEL "B", WITH THOSE CIRCUITS LISTED IN THAT |
| | PANEL.CORRELATE THE PANELS. |
| | |
| | 3} THE POOL PANEL LISTS THE HEATER ON A 20 AMP CIRCUIT, |
| | PANEL "B" LISTS THE HEATER ON A 50 AMP CIRCUIT. |
| | CORRELATE SAME. |
| | |
| | 4} CIRCUITS 9-11 PANEL "B", WATER HEATER LISTS #10 WIRE |
| | ON A 40 AMP BREAKER. SEE 310.16. |
| | |
| | 5} CIRCUITS 10-12, ELEVATOR, SAME AS ABOVE. |
| | |
| | 6} CIRCUIT #29, PANEL "B", MASTER BATH GFCI MUST BE ON |
| | A 20 BREAKER PER 210.11(C)(3). |
| | |
| | 7} THERE ARE 4 A/C SYSTEMS ON THE PANEL SCHEDULE, BUT |
| | ONLY 3 LOCATED ON THE PLAN. |
| | |
| | 8} PER 210.52(E) OUTDOOR OUTLETS FOR A ONE-FAMILY |
| | DWELLING AND EACH UNIT OF A TWO-FAMILY DWELLING THAT IS |
| | AT GRADE LEVEL, AT LEAST ONE RECEPTACLE OUTLET |
| | ACCESSIBLE AT GRADE LEVEL AND NOT MORE THAN 2.0 M (6 1/ |
| | 2 FT) ABOVE GRADE SHALL BE INSTALLED AT THE FRONT AND |
| | BACK OF THE DWELLING. SEE ONE MISSING IN FRONT. |
| | |
| | 9}.SMOKE ALARMS MUST BE INSTALLED TO COMPLY WITH R313.1 |
| | RESIDENTIAL FLORIDA BUILDING CODE. LOCATE ON PLANS |
| | |
| | 10} 210.52(H) HALLWAYS IN DWELLING UNITS, HALLWAYS OF |
| | 3.0 M (10 FT) OR MORE IN LENGTH SHALL HAVE AT LEAST ONE |
| | RECEPTACLE OUTLET. SEE HALLWAY AT BEDROOM #3 AND |
| | LAUNDRY. |
| | |
| | 11} AT LEAST ONE WALL SWITCH CONTROLLED LIGHTING OUTLET |
| | SHALL BE INSTALLED TO PROVIDE ILLUMINATION ON THE |
| | EXTERIOR SIDE OF OUTDOOR ENTRANCES OR EXITS WITH GRADE |
| | LEVEL ACCESS. SEE DOORS IN THE DINING ROOM. |
| | 210.70(A)(2)(B). |
| | |
| | 12} THERE ARE "THEATER" LIGHTS AND RECEPTACLES LISTED |
| | ON THE PANEL SCHEDULE, BUT NO ROOM DESIGNATED FOR THAT |
| | PURPOSE. PLEASE CLARIFY. |
| | |
| | 13} LOCATE THE ELEVATOR ON THE PLANS, CIRCUIT 10-12 |
| | PANEL "B". |
| | |
| | 14} THE GFI RECEPTACLE LOCATED IN BATH #4 EXCEEDS THE |
| | 3' RECEPTACLE SPACING REQUIRED BY 210.52(D) |
| | |
| | 15} RECEPTACLE SPACING MUST COMPLY WITH 210.52(A)(1) |
| | AND 210.52(A)(2) BEDROOM #3. |
| | |
| | 16} LOCATE THE POOL AND "AQUA LOGIC" PANELS ON THE |
| | PLAN. |
| | |
| | NOTE: SHEETS A9 AND A10 ARE MISSING, PLEASE INCLUDE |
| | WHEN RESUBMITTING. |
| | |
| | FLORIDA BUILDING CODE-2004. |
| | |
| | PER 2704.1, 2004 FBC, METAL FRAMING MEMBERS SHALL BE |
| | BONDED TO THE EQUIPMENT GROUNDING CONDUCTOR FOR THE |
| | CIRCUIT THAT MAY ENERGIZE THE FRAMING. PLEASE SEE |
| | ARTICLE. |
| | |
| | SEE 13-606.1.ABC.1.2.3 FBC FOR REQUIREMENTS FOR |
| | RECESSED LIGHTING FIXTURES INSTALLED IN CEILINGS THAT |
| | ABUT AN ATTIC SPACE. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | 561/805-6718 |