| 2007-08-07 13:12:31 | SWIMMING POOL BUILDING REVIEW FIRST CHECKLIST (REVIEW |
| | DONE UNDER FBC 2004 WITH 2006 REVISIONS): |
| | |
| | 1- NEED TO SUBMIT TWO COMPLETE AND EQUAL SETS OF |
| | DRAWINGS AS REQUIRED BY SEC. 106.1 CITY AMENDMENTS TO |
| | FBC 2004.PLANS SUBMITTED DON'T MATCH, WERE SIGNED AND |
| | SEALED ON DIFFERENT DATES AND ONE OF THEM HAS |
| | HANDWRITTENREVISIONS.PLANS NEED TO MATCH AND |
| | HANDWRITTEN INFORMATION IS NOT ALLOWED. ANY CHANGES |
| | SHALL BE DONE ON ORIGINAL DRAWINGS. |
| | |
| | 2- SHEET 1 OF 1:POOL WAS DESIGNED USING THE 2001 |
| | FLORIDA BUILDING CODE.CURRENT CODE IS THE FBC 2004 |
| | AND 2004 FLORIDA RESIDENTIAL CODE.THIS IS A |
| | RESIDENTIAL POOL, THEREFORE CORRECT CODE TO USEIS |
| | CHAPTER 41 OF OF2004 FLORIDA RESIDENTIAL CODE. |
| | ENGINEERING DESIGN SHALL BE DONE AS PER SEC. R4101.6. |
| | REVISE ALL NOTES ON SHEET 1 THAT REFER TO FBC 2001 OR |
| | SECTION 424 OF FLORIDA BUILDING CODE OF 2001. |
| | |
| | 3- POOL SPECIFICATIONS ON SHEET 1 DON'T MATCH DRAWINGS. |
| | EG: SEE POOL DIMENSIONS AND VOLUME. REVISE AS REQUIRED |
| | TO MATCH. |
| | |
| | 4- ENGINEER NEEDS TO USE CURRENT SEAL THAT READS |
| | "LICENSE" INSTEAD OF "CERTIFICATE" AS REQUIRED BY THE |
| | BOARD OF ENGINEERS. |
| | |
| | 5- CLEARLY IDENTIFY WHICH RESIDENTIAL SWIMMING BARRIER |
| | IS GOING TO BE USED AS REQUIRED BY SEC. R4101.17 OF |
| | 2004 FLORIDA RESIDENTIAL CODE. |
| | NOTE: KEEP IN MIND THAT ONE BARRIER IS FROM THE HOUSE |
| | TO THE POOL AND ANOTHER BARRIER REQUIRED IS FROM THE |
| | OUTSIDE OF THE HOUSE. EG: ENTRANCE TO POOL FROM OUTSIDE |
| | GATES. |
| | |
| | 6-POOL VALUE DECLARED ON THE PERMIT APPLICATION WAS |
| | UPDATED TO $45,718, WHICH WAS THE CALCULATED VALUE USED |
| | ON PREVIOUS PERMIT BEFORE IT WAS EXPIRED. OWES $418.50 |
| | AS REQUIRED BY SEC. 108.3 CITY AMENDMENTS TO FBC 2004. |
| | |