| 2007-08-10 07:54:58 | |
| | PLEASE REPLY, IN WRITING OR ON THE PLAN, TO THE |
| | FOLLOWING ARTICLES FROM THE 2005 NEC, WHICH MAY |
| | APPLY.INDICATE SPACING TO THE RECEPTACLES FROM THE |
| | OUTER EDGE OF THE PROPOSED WALL. |
| | |
| | 210.52(A) GENERAL PROVISIONS IN EVERY KITCHEN, FAMILY |
| | ROOM, DINING ROOM, LIVING ROOM, PARLOR, LIBRARY, DEN, |
| | SUNROOM, BEDROOM, RECREATION ROOM, OR SIMILAR ROOM OR |
| | AREA OF DWELLING UNITS, RECEPTACLE OUTLETS SHALL BE |
| | INSTALLED IN ACCORDANCE WITH THE GENERAL PROVISIONS |
| | SPECIFIED IN 210.52(A)(1) THROUGH (A)(3). |
| | (1) SPACING RECEPTACLES SHALL BE INSTALLED SO THAT NO |
| | POINT MEASURED HORIZONTALLY ALONG THE FLOOR LINE IN ANY |
| | WALL SPACE IS MORE THAN 1.8 M (6 FT) FROM A RECEPTACLE |
| | OUTLET. |
| | |
| | DINING ROOMS MUST ALSO COMPLY WITH 210.52(B), SMALL |
| | APPLIANCE RECEPTACLE REQUIREMENT. |
| | |
| | ALSO NOTE SECTION,. R313.1.1, FBC. ALTERATIONS, |
| | REPAIRS AND ADDITIONS. |
| | WHEN INTERIOR ALTERATIONS, REPAIRS OR ADDITIONS |
| | REQUIRING A PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING |
| | ROOMS ARE ADDED OR CREATED IN EXISTING DWELLINGS, THE |
| | INDIVIDUAL DWELLING UNIT SHALL BE PROVIDED WITH SMOKE |
| | ALARMS LOCATED AS REQUIRED FOR NEW DWELLINGS; THE SMOKE |
| | ALARMS SHALL BE INTERCONNECTED AND HARD WIRED. ALSO SEE |
| | EXCEPTION. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | 561/805-6718 |
| | [email protected] |