Plan Review Notes
Plan Review Notes For Permit 07070144
Permit Number 07070144
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2007-08-09 11:37:39*****DENIED*****
  
  
 1.THE CORRECT ADDRESS OF THE PROJECT SITE SHALL BE IN
 THE TITLE BLOCK OF EACH SUBMITTED PLAN SHEET.THE
 ADDRESS CURRENTLY SHOWS ADDRESS AS 1825 MERRY PLACE.
  
 2.SPEC SHEETS APPEAR TO BE OK, HOWEVER AMEND THE
 APPROPIATE COVER SHEETS TO REFLECT THE CORRECT
 ADDRESS.
  
 3.FIRE SPRINKLER SYSTEM IS TO BE MONITORED.
  
 4.COORDINATE WITH THE GENERAL AND/OR OTHER APPROPIATE
 CONTRACTOR(S) THAT THE DOUBLE DETECTOR CHECK ASSEMBLY
 BE CHAINED AND LOCKED UPON COMPLETION OF THE FIRE FINAL
 INSPECTION.
  
 5.COORDINATE WITH THE GENERAL AND/OR OTHER APPROPIATE
 CONTRACTOR(S) THAT THE REQUIRED KNOX LOCKING CAPSBE
 INSTALLED ON THE FIRE DEPARTMENT CONNECTIONS.FOR
 APPLICATIONS, CONTACT WEST PALM BEACH FIRE PREVENTION
 AT 561-805-6722.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE ON THE PLAN EACH ITEM WAS
 ADDRESSED.
  
  