| Plan Review Notes For Permit 07070144 |
| Permit Number |
07070144 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-08-09 11:37:39 | *****DENIED***** | | | | | | | | | 1.THE CORRECT ADDRESS OF THE PROJECT SITE SHALL BE IN | | | THE TITLE BLOCK OF EACH SUBMITTED PLAN SHEET.THE | | | ADDRESS CURRENTLY SHOWS ADDRESS AS 1825 MERRY PLACE. | | | | | | 2.SPEC SHEETS APPEAR TO BE OK, HOWEVER AMEND THE | | | APPROPIATE COVER SHEETS TO REFLECT THE CORRECT | | | ADDRESS. | | | | | | 3.FIRE SPRINKLER SYSTEM IS TO BE MONITORED. | | | | | | 4.COORDINATE WITH THE GENERAL AND/OR OTHER APPROPIATE | | | CONTRACTOR(S) THAT THE DOUBLE DETECTOR CHECK ASSEMBLY | | | BE CHAINED AND LOCKED UPON COMPLETION OF THE FIRE FINAL | | | INSPECTION. | | | | | | 5.COORDINATE WITH THE GENERAL AND/OR OTHER APPROPIATE | | | CONTRACTOR(S) THAT THE REQUIRED KNOX LOCKING CAPSBE | | | INSTALLED ON THE FIRE DEPARTMENT CONNECTIONS.FOR | | | APPLICATIONS, CONTACT WEST PALM BEACH FIRE PREVENTION | | | AT 561-805-6722. | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | LETTER INDICATING WHERE ON THE PLAN EACH ITEM WAS | | | ADDRESSED. | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|