| Date |
Text |
| 2007-09-24 13:18:09 | 2004 FBC W/2007 SUPPLEMENT |
| | LEVEL 2 ALTERATION |
| | 2 STORY ADDITION |
| | |
| | DENIED BY BUILDING |
| | |
| | 1) A RECORDED COPY OF THE NOTICE OF |
| | COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 2) IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY, PLANS STAMPED BY THEM AND |
| | COPY OF RECEIPT SUBMITTED TO CITY OF |
| | WEST PALM BEACH BUILDING DEPARTMENT, |
| | BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| | |
| | 3) ON SHEET S3 THE PLANS SPECIFY ISONYNENE (ICYNENE) |
| | INSULATION, WHICH IS A BRAND NAME FOR SPRAY APPLIED |
| | FOAM INSULATION. THE SPECIFICATIONS AND ICC ES REPORT |
| | THAT WAS SUBMITTED IS FOR SEALECTION 500, WHICH |
| | REQUIRES AN IGNITION BARRIER WHEN INSTALLED IN ATTICS. |
| | PLEASE SPECIFY ON THE PLANS WHICH METHOD OF IGNITION |
| | BARRIER WILL BE INSTALLED (SEE 4.3.1 AND 4.3.2 FROM ES |
| | REPORT ESR-1172). PLEASE REVISE SHEET S3 TO SPECIFY |
| | SPRAY FOAM INSULATION. SEE FBC R 314.5.3. |
| | |
| | 4) THE ARCHITECT'S RESPONSE TO ITEM #8 OF FIRST REVIEW |
| | STATES THAT THE EXISTING WINDOWS AND DOORS WILL NOT BE |
| | REMOVED AND REUSED ON THIS PROJECT. HOWEVER, SHEETS D1, |
| | D2 AND A1 OF THE PLANS STILL SPECIFY REUSING EXISTING |
| | WINDOWS IN THE NEW ADDITION. PLEASE CORRECT. |
| | |
| | 5) THE FINISH GRADE ON THE PROPOSED EAST ELEVATION ON |
| | SHEET A.3 IS MISSING THE NEGATIVE SIGN. PLEASE CORRECT. |
| | |
| | |
| | 6) SPECIFY THE CEILING CLADDING MATERIAL FOR THE |
| | COVERED PORCH ON THE PLANS. SEE ITEM # 24 ON FIRST |
| | REVIEW. |
| | |
| | 7) THE ROOFER WILL SUBMIT RAS 117 CALCULATIONS FOR THE |
| | GAF ROOFING MATERIAL UNDER SEPARATE PERMIT PER RESPONSE |
| | TO ITEM # 33 OF FIRST REVIEW. |
| | |
| | 8)A SEPARATE PERMIT WITH SITE SPECIFIC ENGINEERING |
| | FOR THE CUSTOM CYPRESS FRONT DOOR WILL BE APPLIED FOR |
| | AT A LATER DATE, PER RESPONSE TO ITEM # 35 OF FIRST |
| | REVIEW. |
| | |
| | - ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)805-6714 |
| | [email protected] |