| Plan Review Notes For Permit 07070138 |
| Permit Number |
07070138 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2007-09-24 17:54:13 | 2004 FBC W/2007 SUPPLEMENT | | | LEVEL 2 ALTERATION AND ADDITION | | | | | | DENIED BY BUILDING | | | | | | 1) A RECORDED COPY OF THE NOTICE OF | | | COMMENCEMENT MUST BE SUBMITTED BEFORE A | | | PERMIT CAN BE ISSUED. | | | | | | 2) THE INDEX ON SHEET CH.O DOES NOT LIST SHEETS | | | CHMEP.1, CHS.1 OR CHS.2. | | | | | | 3) SHEET CH.1 IS MISSING FROM THE PLANS. | | | | | | 4) THE ENERGY CALCULATION LISTS TWO BEDROOMS AND ONLY | | | ONE IS SHOWN ON THE PLANS. PLEASE CORRECT. | | | | | | 5) ITEM #7 FROM THE FIRST REVIEW HAS NOT BEEN | | | ADDRESSED. THE EXIT DOOR IS REQUIRED TO PROVIDE DIRECT | | | ACCESS FROM THE HABITABLE PORTION OF THE DWELLING TO | | | THE EXTERIOR. ONE LEAF OF THE DOUBLE DOOR AT THE LIVING | | | ROOM IS REQUIRED TO BE 36" WIDE PER FBC R 311.4.2. | | | | | | 6) ITEM #9 FROM THE FIRST REVIEW HAS NOT BEEN | | | ADDRESSED. SPECIFY THE WINDOW TYPES ON THE PLANS. | | | FBC*106.1.2. | | | | | | 7) HANDWRITTEN CORRECTIONS TO SIGNED AND SEALED | | | DRAWINGS CAN ONLY BE MADE BY THE DESIGNER OF RECORD. | | | THEY ARE REQUIRED TO BE SIGNED AND DATED. FS 481. | | | | | | 8) RESPONSE TO ITEM 25, CONTRACTOR TO SUBMIT RAS 117 | | | CALCULATIONS UNDER A SEPARATE ROOFING PERMIT. | | | | | | -ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] | | | |
|