| Notes |
| Date |
Text |
| 2007-07-12 07:40:30 | | | | | | | | | | NONCOMPLIANT | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE | | | COMPLIANCE AND RESUBMIT FOR REVIEW | | | | | | 1} THE ARCHITECTS SEAL IS INDISCERNIBLE. SEE | | | 61G1-16.001FAC. | | | | | | 2} PROVIDE A LOAD CALCULATION FOR THE ELECTRICAL | | | SERVICE, INDICATING ALL EXISTING LOADS AND ALL LOADS TO | | | BE IMPOSED BY THE ADDITION OF THE NEW EQUIPMENT. 215.5 | | | NEC 2005. | | | | | | 3} SUBMIT A PANEL SCHEDULE PER 408.4 NEC AND | | | 106.3.5.4(8) FBC. ALL PANELS. | | | | | | 4} R313.1.1 SMOKE ALARMS SHALL BE LOCATED AS REQUIRED | | | IN NEW DWELLINGS WHEN REPAIRS OR ADDITIONS REQUIRING A | | | PERMIT OCCUR. SEE ARTICLE FOR COMPLETE TEXT. LOCATE ON | | | THE PLAN. NOTE THE "GUEST ROOM" MEETS THE DEFINITION OF | | | BEDROOM IN THE FBC, AND MUST HAVE SMOKE ALARMS | | | INSTALLED. | | | | | | 5} THE KITCHEN, GUEST ROOM AND LIVING ROOM DO NOT | | | COMPLY WITH RECEPTACLE SPACING REQUIREMENTS OF | | | 210.52(A)(1) & (2). | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | | [email protected] |
|