Plan Review Notes
Plan Review Notes For Permit 07070130
Permit Number 07070130
Review Stop B
Sequence Number 2
Notes
Date Text
2007-08-30 09:04:14BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6652
 E-MAIL: [email protected]
  
 FBC = FLORIDA BUILDING CODE 2004 (WITH 2007
 AMENDMENTS)
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
 F.S.= FLORIDA (STATE) STATUTE
  
 1) FBC* 106.1 AND 471.025 F.S.ENGINEERS SEAL AND
 SIGNATURE.THE SUBMITTED PLANS HAVE AN ENGINEER'S
 TITLE BLOCK BUT THE PLANS ARE PHOTOCOPIES.THEY DO NOT
 HAVE THE ORIGINAL SIGNATURE AND RAISED SEAL OF THE
 ENGINEER.SUBMIT SIGNED AND SEALED ORIGINALS.
  
 2) FBC 2002.4TRAC SELF MATING BEAM.SHEET 2 OF THE
 SUBMITTED PRODUCT APROVAL FL 7350.1 STATES THAT "SITE
 SPECIFIC ENGINEERING MUST ACCOMPANY THIS PRODUCT
 APPROVAL FOR EACH STRUCTURE INSTALLED".NO SITE SITE
 SPECIFIC ENGINEERING WAS SUBMITTED.SUBMIT SITE
 SPECIFIC ENGINEERING TO JUSTIFY THE MEMBER SIZES FOR
 THE PROPOSED SPANS AND CONFIGURATION.
  
 3) FBC 2002.4CORNER POSTS.THE CORNER POST SIZE (AND
 WALL THICKNESS) IS NOT STATED ON THE PLANS.
  
 4) FBC 2002.4PURLIN AND ROOF BRACE SIZES ARE STATED
 ON THE CONNECTION DETAILS BUT ARE NOT STATED ON THE
 PLAN VIEW OF THE STRUCTURE.THE CONNECTION DETAILS ARE
 ENGINEERED (SEE COMMENT 1) BUT THEY ARE NOT CORRELATED
 WITH THE LAYOUT PLAN (SEE COMMENT 2 ABOVE).
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO TELEPHONE:
 (561) 805 6652ROBERT BROWN
 E-MAIL: [email protected]