| 2007-07-18 10:13:54 | BUILDING REVIEW CHECKLIST: |
| | 1- SETBACKS SHOWN ON SITE PLAN DON'T MATCH SURVEY. |
| | |
| | 2- FLOOD ZONE INFORMATION ON SURVEY IS INCORRECT. |
| | PROPERTY IS LOCATED IN FLOOD ZONE "C" PER COMMUNITY |
| | PANEL # 120229 0020 B DATED MARCH 01, 1979.REVISE AS |
| | REQUIRED. THIS IS THE ONLY OFFICIAL MAP TO BE USED FOR |
| | FLOOD ZONE DETERMINATION. |
| | |
| | 3- PROVIDE COMPLETE SPECS FOR ICYNENE INSULATION.AND |
| | CLARIFY IF EXISTING RESIDENCE HAS THIS TYPE OF |
| | INSULATION TO VERIFY COMPLIANCE WITH ATTIC VENTILATION |
| | SEC. R806 OF 2004 FLORIDA RESIDENTIAL CODE. SEC. |
| | 106.1.2 CITY AMENDMENTS TO FBC 2004. |
| | |
| | 4- SPECIFY DESIGN CRITERIA AND CODE TO BE USED AS |
| | REQUIRED BY SEC. R301 AND TABLE R301.5 OF 2004 FLORIDA |
| | RESIDENTIAL CODE. SPECIFY ALLWIND, LIVE AND DEAD |
| | LOADS. |
| | |
| | 5- SPECIFY CONSTRUCTION TYPE AS REQUIRED BY SEC. 602.1 |
| | FBC 2004. |
| | |
| | 6- SPECIFY ROOF TILE FASTENING AS REQUIRED BY SEC. |
| | 106.1.1.2 CITY AMENDMENTS TO FBC 2004. PROVIDE COMPLETE |
| | SPECS NAIL OR SCREW SIZE AND NUMBER OR SPECIFIC |
| | ADHESIVE TO VERIFY COMPLIANCE WITH THE ATTACHMENT |
| | RESISTANCE. PRODUCT APPROVAL IS TO VERIFY COMPLIANCE |
| | WITH DESIGNER CRITERIA. |
| | |
| | 7- PROVIDE PRODUCT APPROVAL AS REQUIRED BY DCA RULE |
| | 9B-72 FOR: |
| | A) ROOF TILE.NEED TO PROVIDE COMPLETE REPORT AS |
| | DONE WITH WINDOWS AND DOORS. ONLY THE FLORIDA PRODUCT |
| | APPROVAL COVER PAGES INFORMATION WAS PROVIDED. |
| | |
| | B) ALL SIMPSON STRUCTURALCONNECTORS SPECIFIED ON |
| | PLANS. NEED TO PROVIDE THE PRODUCT APPROVAL COVER PAGE |
| | AND THE SPECIFIC PAGE WHERE CONNECTOR IS SHOWN. ONLY |
| | THE COVER PAGE WAS PROVIDED. |
| | |
| | 8- ENERGY CALCULATIONS: |
| | A) OWNER/AGENT TO SIGN AND DATE CALCULATIONS AT |
| | BOTTOM OF FORM. |
| | |
| | B) PROVIDE COMPLETE INFORMATION, INCLUDING BUILDER |
| | INFORMATION. |
| | |
| | 9- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| | REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004. |
| | |
| | |