Plan Review Notes
Plan Review Notes For Permit 07070123
Permit Number 07070123
Review Stop P
Sequence Number 1
Notes
Date Text
2007-07-31 07:25:52DENIED;
 1. SHOW DETAILS OF HANDICAP BATHROOM FIXTURES WITH ALL
 MESSUREMENTS REQUIRED. SEE FBC-2004 BUILDING CHAPTER 11
 FIG'S 29 & 32.
 2. BATHROOM DOOR CANNOT SWING INTO THE CLEAR FLOOR
 SPACE OF THE LAVATORY.
 3. THE TURNING RADIUS IS 5' NOT 3' AS SHOWN ON
 DRAWING.
 4. SHOW WATER RISER DIAGRAM AS REQUIRED BY FBC-2004
 BUILDING CHAPTER 1, SECTION 106.3.5.1.3. PLUMBING NOTES
 4 AND 9 REFERENCE WATER HEATER, NOT SHOWN ON DRAWINGS.
 PLUMBING PLAN REVIEW BY;