| Plan Review Notes For Permit 07070123 |
| Permit Number |
07070123 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-07-31 07:25:52 | DENIED; | | | 1. SHOW DETAILS OF HANDICAP BATHROOM FIXTURES WITH ALL | | | MESSUREMENTS REQUIRED. SEE FBC-2004 BUILDING CHAPTER 11 | | | FIG'S 29 & 32. | | | 2. BATHROOM DOOR CANNOT SWING INTO THE CLEAR FLOOR | | | SPACE OF THE LAVATORY. | | | 3. THE TURNING RADIUS IS 5' NOT 3' AS SHOWN ON | | | DRAWING. | | | 4. SHOW WATER RISER DIAGRAM AS REQUIRED BY FBC-2004 | | | BUILDING CHAPTER 1, SECTION 106.3.5.1.3. PLUMBING NOTES | | | 4 AND 9 REFERENCE WATER HEATER, NOT SHOWN ON DRAWINGS. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|