| 2007-07-17 08:30:57 | *** DENIED *** | | | 1) PLANS DO NOT INDICATE WHAT IS NEW, EXISTING, OR | | | REPLACEMENT. PLEASE CORRECT. | | | | | | 2) PLEASE SUBMIT ENERGY CALCULATIONS, SEE 2004 FBC | | | 13-101.1.3. | | | | | | 3) PLEASE SUBMIT COOLING LOAD CALCULATIONS, SEE 2004 | | | FBC 13-407.1.ABC.1. | | | | | | 4) PLEASE SHOW ON MECHANICAL PLANS AN A/C EQUIPMENT | | | SCHEDULE WITH ALL PERTINENT INFORMATION. | | | | | | 5) SHOW ON MECHANICAL PLANS OUTSIDE AIR CALCULATIONS, | | | AND PROVIDE OUTSIDE AIR, SEE 2004 FBC 401.2. | | | | | | 6) SHOW ALL DUCT AND GRILL SIZES ON PLANS. | | | | | | 7) SHOW SUPPLY AIR CFM'S. AT ALL SUPPLY AIR GRILLS. | | | | | | 8) SHOW BATHROOM EXHAUST FAN ON MECHANICAL PLANS, SEE | | | 2004 FBC/M 403.3. | | | | | | 9) SHOW LOCATION OF A/C CONDENSER UNIT ON PLANS. | | | | | | 10) SHOW HOW AIR IS TO RETURN TO THE AIR HANDLER UNIT | | | FROM THE FIRST AND SECOND FLOOR. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. | | | |
|