2007-07-17 08:30:57*** DENIED ***
 1) PLANS DO NOT INDICATE WHAT IS NEW, EXISTING, OR
 REPLACEMENT. PLEASE CORRECT.
  
 2) PLEASE SUBMIT ENERGY CALCULATIONS, SEE 2004 FBC
 13-101.1.3.
  
 3) PLEASE SUBMIT COOLING LOAD CALCULATIONS, SEE 2004
 FBC 13-407.1.ABC.1.
  
 4) PLEASE SHOW ON MECHANICAL PLANS AN A/C EQUIPMENT
 SCHEDULE WITH ALL PERTINENT INFORMATION.
  
 5) SHOW ON MECHANICAL PLANS OUTSIDE AIR CALCULATIONS,
 AND PROVIDE OUTSIDE AIR, SEE 2004 FBC 401.2.
  
 6) SHOW ALL DUCT AND GRILL SIZES ON PLANS.
  
 7) SHOW SUPPLY AIR CFM'S. AT ALL SUPPLY AIR GRILLS.
  
 8) SHOW BATHROOM EXHAUST FAN ON MECHANICAL PLANS, SEE
 2004 FBC/M 403.3.
  
 9) SHOW LOCATION OF A/C CONDENSER UNIT ON PLANS.
  
 10) SHOW HOW AIR IS TO RETURN TO THE AIR HANDLER UNIT
 FROM THE FIRST AND SECOND FLOOR.
  
 MECHANICAL PLAN REVIEW BY;