Plan Review Notes
Plan Review Notes For Permit 07070123
Permit Number 07070123
Review Stop E
Sequence Number 1
Notes
Date Text
2007-07-13 17:46:14 
  
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW
  
 1} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST
 PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.3. FBC.
 IF AN ARCHITECT OR ENGINEER, COMPLY WITH 418 AND 417
 FS, RESPECTIVELY.
  
 2} DECLARE THE USE OF THE BUILDING PER CHAPTER 3, FBC..
 CHANGE OF OCCUPANCY. A CHANGE IN THE PURPOSE OR LEVEL
 OF ACTIVITY WITHIN A BUILDING THAT INVOLVES A CHANGE IN
 APPLICATION OF THE REQUIREMENTS OF THIS CODE.
  
 3} PANEL MAY NOT BE LOCATED IN A STORAGE CLOSET PER
 240.24(D).
  
 4} INDICATE IF ALL WORK SHOWN IS NEW UNDER THIS
 APPLICATION. IF THERE IS EXISTING INDICATE SAME.
  
 5} PROVIDE CIRCUIT NUMBERS FOR ALL DEVICES 106.3.5.1.2
 FBC. SEE LOFT.
  
 6} PLEASE INDICATE THE CODE CYCLES THIS PROJECT WAS
 DESIGNED UNDER. 2004 FBC, 2005 NEC ETC. ADD TO NOTES
 FOR CLARITY IN THE FIELD.
  
 7} 301.5 A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT
 ONE OR A COMBINATION OF LEVELS OF ALTERATION PURSUANT
 TO SECTIONS 303, 304 AND 305 OF THIS CODE. EXISTING
 BUILDING CODE, 2004 FBC.
  
 8} INDICATE COMPLIANCE WITH CHAPTER 13
 OF THE FLORIDA BLDG CODE. 13.413,
 13.414, 13.415. SHOW TIME CLOCK AND/OR
 OCCUPANCY SENSOR LOCATIONS ON THE PLAN.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718