Notes
Date Text
2007-07-09 12:20:20FOR PLAN REVIEW ONLY NOT FOR PERMIT.
 *** DENIED ***
 1) PLEASE PROVIDE COOLING LOAD CALCULATIONS, SEE 2004
 FBC 13-407.1.ABC.1.
  
 2) PLEASE PROVIDE OUTDOOR AIR CALCULATIONS, SEE 2004
 FBC/M 401.2. AND PLEASE STATE WHAT TYPE OF BUSINESS
 THESE ARE.
  
 3) SUITE 422, PLEASE PROVIDE RETURN AIR TO WHAT APPEARS
 TO BE AN 8 X 10 FT. OFFICE, SEE 2004 FBC/M 601.4.
  
 4) SUITE 420, PLEASE SHOW HOW AIR WILL RETURN TO THE
 AHU AS IT APPEARS TO BE IN A 9 X 12 FT. OFFICE.
  
 5)INFORMATION MISSING IN TITLE BLOCK FOR ARCHITECT
 (FIRM LICENSE NUMBER) LICENSE NUMBER IN TITLE BLOCK
 AR0011209 IS FOR ROGER GILMAN MORSE NOT FOR THE FIRM
 MORSE ASSOCIATES. PLEASE CORRECT, SEE FAC 61G1-16.004
 TITLE BLOCK.
 A TITLE BLOCK MUST APPEAR ON ALL ARCHITECTURAL OR
 INTERIOR DESIGN DRAWINGS AND SPECIFICATION
 IDENTIFICATION SHEETS. THE TITLE BLOCK MUST, AT A
 MINIMUM, CONTAIN THE FOLLOWING INFORMATION:
 (1) FIRM NAME, ADDRESS, AND TELEPHONE NUMBER.
 (2) FIRM LICENSE NUMBER.
 (3) NAME OR IDENTIFICATION OF PROJECT. ("JOB ADDRESS"
 SEE CITY WPB AMEND. 106.1.1).
 (4) DATE PREPARED.
 (5) A SPACE FOR THE SIGNATURE AND DATED SEAL.
 (6) A SPACE FOR THE PRINTED NAME OF THE PERSON SEALING
 THE DOCUMENT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.