| Plan Review Notes For Permit 07070110 |
| Permit Number |
07070110 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-07-24 16:27:43 | *****DENIED***** | | | | | | | | | 1.ONLY ONE PLAN SET (UNDER THIS PERMIT NUMBER) WAS | | | SUBMITTED FOR REVIEW.AT LEAST TWO BUT NO MORE THAN | | | THREE SIGNED, DATED AND SEALED SET OF PLANS ARE TO BE | | | SUBMITTED. | | | | | | 2.THE NUMERICAL ADDRESS SHALL BE IN THE TITLE BLOCK | | | OF EACH SUBMITTED PLAN SHEET. THERE ARE TWO STRUCTURES | | | ON THIS SITE, PLEASE INDICATE THE ADDRESSED STRUCTURE. | | | | | | 3.ON SHEET 6 (OF 9), FIRE HYDRANT (F.H.) #2 APPEARS | | | TO BE LOCATED BETWEEN TWO PARKING SPACES.THE FIRE | | | DEPARTMENT SHALL NOT BE DETERRED OR HINDERED FROM | | | GAINING IMMEDIATE ACCESS TO FIRE PROTECTION EQUIPMENT. | | | | | | | | | | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|