| 2007-07-26 19:15:34 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBCFLORIDA BUILDING CODE 2004 | | | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING | | | CODE | | | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC* | | | CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC | | | FLORIDA ADMINISTRATIVE CODE | | | FSFLORIDA STATUTE | | | | | | 1.)PROVIDE A FLOOR PLAN SHOWING LOCATION OF THE SGD'S | | | AND WINDOWS. | | | | | | 2.)FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED | | | IN ADDITION TO THE NOA SUBMITTED, FAC9B72. | | | WWW.FLORIDABUILDING.ORG | | | | | | SEE SHEET 1 OF 6 (DRAWINGS IN THE PRODUCT APPROVAL).A | | | 33% INCREASE IN ALLOWABLE STRESS WAS USED IN ANCHOR | | | DESIGN.THIS IS NOT PERMITTED IN THE FLORIDA BUILDING | | | CODE.IN ORDER FOR A LOCAL PRODUCT APPROVAL TO BE | | | ISSUED USING THE NOA, SUBMIT A LETTER FROM THE ENGINEER | | | STATING THAT THE ANCHORING IS ACCEPTABLE WITHOUT THE | | | STRESS INCREASE, OR SUBMIT THE REVISED NOA. | | | | | | 3.)PRODUCT APPROVALS ARE TO BE APPROVED BY DESIGNER | | | OF RECORD (SHOP DRAWING REVIEW STAMP OR LETTER), | | | FBC*106.3.3. | | | | | | 4.)PROVIDE CONDO ASSOCIATION APPROVAL. | | | | | | 5.)DOCUMENTS ARE NOT LEGIBLE, FBC*106.1.2. | | | | | | 6.)THE WINDOWS DO NOT APPEAR TO BE COMPLIANT WITH THE | | | DESIGN PRESSURES FOR THE BUILDING. |
|