| Plan Review Notes For Permit 07070074 |
| Permit Number |
07070074 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2007-08-30 10:08:17 | BUILDING PLAN REVIEW | | | *******DENIED******* | | | ROBERT BROWN(561) 805 6652 | | | E-MAIL: [email protected] | | | | | | FBC = FLORIDA BUILDING CODE 2004 (WITH 2007 | | | AMENDMENTS) | | | FBC*= FLORIDA BUILD'G CODE (CITY AMEND) | | | F.S.= FLORIDA (STATE) STATUTE | | | | | | 1) FBC 1609.1SHUTTER ATTACHMENT.THE SUBMITTED | | | SHUTTER INSTALLATION SCHEDULE STATES THAT THE ANCHORS | | | WILL BE 1/4" DIA. X 1-1/4" LONG ELCO/BUILDIEX HEX HEAD | | | MAXISET TAPCON.THAT LENGTH WILL NOT PROVIDE ENOUGH | | | EMBEDMENT.PAGE 14 OF THE SUBMITTED AMERICAN SHUTTER | | | SYSTEMS PRODUCT APPROVAL (FL 7279-R1) STATES THAT | | | 1-3/4" EMBEDMENT IS REQUIRED FOR POURED CONCRETE | | | SUBSTRATE AND 1-1/4" EMBEDMENT IS REQUIRED FOR CONCRETE | | | BLOCK SUBSTRATE. EITHER PROVIDE LONGER ANCHORS OR | | | SPECIFY ONE OF THE OTHER ANCHOR TYPE/SIZE OPTIONS | | | STATED IN THE PRODUCT APPROVAL. | | | | | | **QUOTE PERMIT# ON ALL CORRESPONDENCE** | | | | | | END OF REVIEW COMMENTS | | | THE CODE REFERENCES GIVE ADDITIONAL INFO TELEPHONE: | | | (561) 805 6652ROBERT BROWN | | | E-MAIL: [email protected] |
|