Plan Review Notes
Plan Review Notes For Permit 07070072
Permit Number 07070072
Review Stop M
Sequence Number 1
Notes
Date Text
2007-07-10 15:00:30*** DENIED ***
 1) ENERGY CALCULATIONS ARE SHOWING ONE 30,200 BTU A/C
 SYSTEM, PLANS PAGE MP-1 EQUIPMENT SCHEDULE IS SHOWING
 TWO 30,200 BTU A/C SYSTEMS THE TWO MUST COINCIDE,
 PLEASE CORRECT.
  
 2) ENERGY CALCULATIONS ARE SHOWING A 19 SEER A/C
 SYSTEM, PLANS PAGE MP-1 IS SHOWING TWO 13 SEER A/C
 SYSTEMS THE TWO MUST COINCIDE, PLEASE CORRECT.
  
 3) ENERGY CALCULATIONS ARE TAKING A CREDIT FOR CEILING
 FAN, PLANS SHOW NO CEILING FANS, SEE 2004 FBC
 13-607.1.A.1, PLEASE CORRECT.
  
 4) PLANS SHOW THE AIR HANDLERS IN A CLOSET WITH A
 CLOTHES WASHER AND DRYER THIS MAY NOT BE DONE SEE 2004
 FBC 13-601.1.ABC.3.7, PLEASE CORRECT.
  
 5) PLEASE CORRECT COOLING LOAD CALCULATIONS (MANUAL J)
 TO SHOW TWO ZONES AND TWO SYSTEMS.
  
 6) PLEASE SUBMIT MECHANICAL PLANS THAT SHOW THE A/C
 DUCT DESIGN AND ALL OTHER PERTINENT INFORMATION.
  
 7) PLEASE SUBMIT DETAILED MANUFACTURER'S
 SPECIFICATION'S AND INSTALLATION INSTRUCTIONS FOR WOOD
 FIRE PLACE.
  