2007-07-10 08:55:34 
  
 DENIED/INCOMPLETE INFORMATION
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 301.5 A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE
 OR A COMBINATION OF LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 303, 304 AND 305 OF THIS CODE.
  
 1} SUBMIT A PANEL SCHEDULE PER 408.4 NEC AND
 106.3.5.4(8) FBC.408.4 CIRCUIT DIRECTORY OR CIRCUIT
 IDENTIFICATION
 EVERY CIRCUIT AND CIRCUIT MODIFICATION SHALL BE LEGIBLY
 IDENTIFIED AS TO ITS CLEAR, EVIDENT, AND SPECIFIC
 PURPOSE OR USE. THE IDENTIFICATION SHALL INCLUDE
 SUFFICIENT DETAIL TO ALLOW EACH CIRCUIT TO BE
 DISTINGUISHED FROM ALL OTHERS THE SCHEDULE GIVEN DOES
 NOT REFLECT THE REQUIRED CIRCUITS PER 210.11.
  
 2} SMOKE ALARMS MUST BE INSTALLED TO COMPLY WITH R313.1
 RESIDENTIAL FLORIDA BUILDING CODE.LOCATE SAME ON PLANS
 TO INDICATE COMPLIANCE.
  
 3} THE AHU @ 5KW IN THE CALCULATION (AND PANEL
 SCHEDULE), SHEET E-1, DONOT MATCH THE SPECIFICATIONS ON
 SHEET MP-1, @ 9.6 KW. PLEASE CORRELATE.
  
 4} THE DISCONNECTING MEANS FOR THE RELOCATED CONDENSING
 UNITS MUST COMPLY WITH THE CLEARANCE REQUIREMENTS OF
 110.26.
  
 NOTE: REGARDING ELECTRICAL NOTE #18, SHEET E-1,
 ALTHOUGH THERE IS NO VIOLATION WITH THIS INSTALLATION,
 IT IS REQUIRED IN COMMERCIAL BUILDINGS ONLY. IF THE
 NOTE REMAINS ON THE PLAN, THE SYSTEM MUST BE INSTALLED
 OR A REVISION WILL BE REQUIRED TO REMOVE THE NOTE FROM
 THE PLAN. ALSO VERIFY NOTE #17.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]