| 2007-07-10 08:55:34 | |
| | |
| | DENIED/INCOMPLETE INFORMATION |
| | |
| | PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE |
| | COMPLIANCE AND RESUBMIT FOR REVIEW. |
| | |
| | 301.5 A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE |
| | OR A COMBINATION OF LEVELS OF ALTERATION PURSUANT TO |
| | SECTIONS 303, 304 AND 305 OF THIS CODE. |
| | |
| | 1} SUBMIT A PANEL SCHEDULE PER 408.4 NEC AND |
| | 106.3.5.4(8) FBC.408.4 CIRCUIT DIRECTORY OR CIRCUIT |
| | IDENTIFICATION |
| | EVERY CIRCUIT AND CIRCUIT MODIFICATION SHALL BE LEGIBLY |
| | IDENTIFIED AS TO ITS CLEAR, EVIDENT, AND SPECIFIC |
| | PURPOSE OR USE. THE IDENTIFICATION SHALL INCLUDE |
| | SUFFICIENT DETAIL TO ALLOW EACH CIRCUIT TO BE |
| | DISTINGUISHED FROM ALL OTHERS THE SCHEDULE GIVEN DOES |
| | NOT REFLECT THE REQUIRED CIRCUITS PER 210.11. |
| | |
| | 2} SMOKE ALARMS MUST BE INSTALLED TO COMPLY WITH R313.1 |
| | RESIDENTIAL FLORIDA BUILDING CODE.LOCATE SAME ON PLANS |
| | TO INDICATE COMPLIANCE. |
| | |
| | 3} THE AHU @ 5KW IN THE CALCULATION (AND PANEL |
| | SCHEDULE), SHEET E-1, DONOT MATCH THE SPECIFICATIONS ON |
| | SHEET MP-1, @ 9.6 KW. PLEASE CORRELATE. |
| | |
| | 4} THE DISCONNECTING MEANS FOR THE RELOCATED CONDENSING |
| | UNITS MUST COMPLY WITH THE CLEARANCE REQUIREMENTS OF |
| | 110.26. |
| | |
| | NOTE: REGARDING ELECTRICAL NOTE #18, SHEET E-1, |
| | ALTHOUGH THERE IS NO VIOLATION WITH THIS INSTALLATION, |
| | IT IS REQUIRED IN COMMERCIAL BUILDINGS ONLY. IF THE |
| | NOTE REMAINS ON THE PLAN, THE SYSTEM MUST BE INSTALLED |
| | OR A REVISION WILL BE REQUIRED TO REMOVE THE NOTE FROM |
| | THE PLAN. ALSO VERIFY NOTE #17. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | 561/805-6718 |