| 2007-08-14 19:04:29 | PROJECT: 205 SOUTHERN BLVD. |
| | |
| | PROJECT DETAIL: INSTALL FREE STANDING AWNING/CANOPY |
| | |
| | PLAN REVIEW: 2004 FLORIDA BUILDING CODE W/2006 |
| | REVISIONS |
| | |
| | |
| | COMMENTS: |
| | |
| | 1) PLEASE SHOW THE EXISTING CONCRETE SLAB THICKNESS. |
| | |
| | 2) PLEASE INDICATE THE HEIGHT OF THE STRUCTURE: |
| | |
| | 3105.1.1 LOCATION. |
| | |
| | 3105.1.1.1 |
| | FABRIC AWNINGS AND FABRIC-COVERED FRAMES LOCATED OVER |
| | PUBLIC PROPERTY OR IN AREAS ACCESSIBLE TO THE GENERAL |
| | PUBLIC SHALL BE CONSTRUCTED SO THAT NO RIGID PART OF |
| | SUCH FABRIC AWNINGS OR FABRIC-COVERED FRAMES SHALL BE |
| | LESS THAN 7 FEET, 6 INCHES (2286 MM) FROM THE GRADE |
| | DIRECTLY BELOW, AND NO PART OF THE CLOTH DROP SHALL BE |
| | LESS THAN 7 FEET (2134 MM). |
| | 3105.1.1.2 |
| | A FIXED FABRIC AWNING OR FABRIC-COVERED FRAME SHALL NOT |
| | EXTEND OVER PUBLIC PROPERTY MORE THAN TWO-THIRDS THE |
| | DISTANCE FROM THE PROPERTY LINE TO THE NEAREST CURB |
| | LINE IN FRONT OF THE BUILDING SITE AS MEASURED FROM THE |
| | EXTERIOR FACE OF THE BUILDING NOR SHALL ANY PORTION BE |
| | CLOSER THAN 18 INCHES (457 MM) TO THE CURB LINE. |
| | EXCEPTIONS: |
| | 1. IF INSTALLED OVER 14 FEET (4267 MM) IN HEIGHT, IT |
| | MAY OCCUPY THE ENTIRE WIDTH OF THE SIDEWALK. 2. UNLESS |
| | OTHERWISE REGULATED BY LOCAL ZONING REQUIREMENTS. |
| | |
| | 3)INDICATE THE TYPE AND SPACING OF THE PIPE TRUSSES. |
| | |
| | 4) SHOW THAT THE AWNING FABRIC IS A QUICK REMOVAL |
| | SYSTEM: |
| | |
| | 3105.4.2.1 |
| | THE WIND DESIGN LOADS FOR ANY FABRIC OR |
| | MEMBRANE-COVERED STRUCTURE DESIGNED WITH A QUICK |
| | REMOVAL OR BREAKAWAY MEMBRANE OR FABRIC AT WIND |
| | VELOCITIES OF 75 MPH, SHALL BE BASED ON THE FOLLOWING |
| | CRITERIA: |
| | 1. MINIMUM WIND VELOCITY OF 3-SECOND WIND GUST 90 MPH |
| | 2. IMPORTANCE FACTOR BASED ON LOW HAZARD TO HUMAN LIFE |
| | OF 0.77. |
| | 3. EXPOSURE CATEGORY B FOR OR C AS DEFINED IN CHAPTER |
| | 16. |
| | |
| | |
| | REVIEW: KEN CONRAD |
| | PHONE: 561.805.6666 |
| | |