| 2007-09-12 09:09:37 | ***FAILED*** |
| | |
| | |
| | 1)TWO (2) SETS OF ALL REVISED PLANS SHALL BE |
| | SUBMITTED. |
| | |
| | 2)ELEVATIONS SHALL BE LABELED INDICATING WHICH |
| | STREET FRONTAGE IT FACES. |
| | |
| | 3)PROVIDE TWO (2) COPIES OF A CURRENT SURVEY. |
| | |
| | 4)PURSUANT TO SECTION 94-219(D)(9)(A) OF THE ZONING |
| | AND LAND DEVELOPMENT REGULATIONS:ALL PROPERTIES |
| | SHALL BE BROUGHT INTO COMPLIANCE WITH THE LANDSCAPE |
| | REGULATIONS IN ARTICLE XIV, CONCURRENTLY WITH EXTERIOR |
| | BUILDING IMPROVEMENTS EXCEEDING $10,000.00. PLEASE |
| | PROVIDE A LANDSCAPE PLAN INDICATING SUCH. |
| | |
| | 5)PLANS SHALL SHOW COMPLIANCE WITH SECTION 94-221, |
| | SPECIFICALLY WITH REGARD TO THE FIRST FLOOR GLAZING |
| | REQUIREMENTS, THE WINDOWS 2" DEPTH SETBACK, AND THE |
| | WINDOW OPENINGS 2' SETBACK FROM THE CORNERS OF THE |
| | BUILDING. |
| | |
| | 6)PLANS A-1 SHOW A "FUTURE CEILING HEIGHT" OF 9' , |
| | THE CEILING WILL NOT BE PERMITTED TO A LOWER LEVEL THAN |
| | WHAT IS EXISTING AS IT IS NONCONFORMING WITH RESPECT TO |
| | SECTION 94-221(A)(3):STORIES AT THE SIDEWALK LEVEL |
| | SHALL BE NO LESS THAN 12 FEET IN HEIGHT FROM FINISHED |
| | FLOOR TO FINISHED CEILING AND SHALL NOT EXCEED 16 FEET |
| | IN HEIGHT FROM FINISHED FLOOR TO FINISHED FLOOR. |
| | MEZZANINES THAT EXCEED THE PERMISSIBLE PERCENTAGE OF |
| | FLOOR AREA FOR A MEZZANINE AS DEFINED IN THE CITY'S |
| | BUILDING CODE SHALL BE COUNTED AS A STORY. |
| | |
| | |
| | QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS, ZONING |
| | TECHNICIAN |
| | (561)805-6720 |