| 2007-07-26 18:07:29 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBCFLORIDA BUILDING CODE 2004 |
| | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING |
| | CODE |
| | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL |
| | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 |
| | FAC FLORIDA ADMINISTRATIVE CODE |
| | FSFLORIDA STATUTE |
| | |
| | 1.)PRODUCT APPROVALS ARE TO BE APPROVED BY DESIGNER |
| | OF RECORD (SHOP DRAWING REVIEW STAMP OR LETTER), |
| | FBC*106.3.3. |
| | |
| | 2.)FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED |
| | IN ADDITION TO THE NOA SUBMITTED, FAC9B72. |
| | WWW.FLORIDABUILDING.ORG |
| | |
| | 3.)INCLUDE A CODE SUMMARY; BUILDING TYPE FBC6, |
| | BUILDING HEIGHT AND AREA FBC5, SPRINKLER INFORMATION, |
| | OCCUPANCY CLASSIFICATION FBC 3 AND AREA PER OCCUPANCY. |
| | |
| | 4.)DECLARE WIND DESIGN CRITERIA, FBC1603.1.4. |
| | |
| | 5.)SHOW HOW EGRESS IS AFFECTED BY THE ELIMINATION OF |
| | THE DOOR. |
| | |
| | 6.)IMPACT PROTECTION IS REQUIRED, FBC1609.1.4. |
| | |
| | 7.)USE OF REMOVABLE SHUTTERS ON COMMERCIAL PROPERTIES |
| | REQUIRES APPROVAL FROM THE BUILDING OFFICIAL.IF YOU |
| | ARE PROPOSING TO USE REMOVABLE SHUTTERS, SUBMIT A |
| | HURRICANE INSTALLATION PLAN, SEE ATTACHED POLICY, ITEM |
| | 13.PROVIDE PRODUCT APPROVALS AND COMPLETE AN |
| | INSTALLATION SCHEDULE. |
| | |
| | 8.)THE DOORS PROPOSED ARE NOT FOR USE WHERE WATER |
| | INFILTRATION RESISTANCE IS REQUIRED.SHOW (ON THE |
| | PLAN) WHY WATER INFILTRATION RESISTANCE IS NOT |
| | REQUIRED.SEE FBC1714.5.2.1, EXCEPTIONS. |
| | |
| | 9.)PROVIDE PRODUCT APPROVALS FOR THE STOREFRONT. |
| | |
| | 10.)DETAIL A USES THE WORD "HUBGYGYVBGY".WHAT IS |
| | THIS?THE PURPOSE OF PLANS IS TO SHOW CODE COMPLIANCE |
| | OR FOR CONSTRUCTION.THE PURPOSE OF THIS NOTE IS NOT |
| | CLEAR. |
| | |
| | 11.)THE PLAN SHOWS A 2X4 ALUMINUM TUBE, A GLASS |
| | PANEL.WINDOWS ARE TO BE TESTED IN ACCORDANCE WITH |
| | FBC1714.5.PLEASE MAKE SCOPE OF WORK AND |
| | SPECIFICATIONS CLEAR ON THE PLAN. |
| | |
| | |
| | |