| Plan Review Notes For Permit 07070044 |
| Permit Number |
07070044 |
|
| Review Stop |
P |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2008-01-09 09:53:19 | DENIED; | | | LAST PLUMBING REVIEW COMMENTS WERE NOT ADDRESSED; COPY | | | OF LAST PLAN REVIEW ATTACHED | | | 1. (NOT ADDRESSED) PAGE M-3 "COLD WATER MAKE-UP DETAIL" | | | JUMPER AROUND BACKFLOW PREVENTER IS NOT PERMITED. | | | SUBMIT INFORMATION ON BACKFLOW TO BE INSTALLED. | | | 2. (NOT ADDRESSED) SANITARY RISER DIAGRAM; (ONE SET | | | MARKED) | | | A)KITCHEN SINK SHOWN IN TWO PLACES, SINK | | | CANNOT DISCHARGE THRU A BATHROOM GROUP. SECTION 909.1. | | | B) HORIZONTAL DRY VENTS NOT PERMITED | | | SECTION 905.3 | | | C) W/M STAND PIPE NOT REQUIRED TO HAVE AN | | | AIR HAMMER DEVISE. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|