| Notes |
| Date |
Text |
| 2007-10-20 09:46:02 | DENIED; | | | 1. PAGE M-3 COLD WATER MAKE-UP DETAIL; 1" COLD WATER | | | JUMPER AROUND BACKFLOW PREVENTER NOT PERMITED. CHECK | | | VALVES CAN NOT BE TESTED AND MAY FAIL (INSTALLED ON | | | BY-PASS). SUBMIT MANUFACTURE AND MOTEL NUMBER OF | | | BACKFLOW. | | | 2. SANITARY RISER DIAGRAM; ( MARKED ON ONE SET OF | | | PLANS. | | | A) 2 KITCHEN SINKS SHOWN ON RISER DIAGRAM ONLY | | | ONE ON PLANS, PLEASE CORRECT. | | | B) HORIZONTALDRY VENTS NOT PERMITED SEE FBC | | | PLUMBING SECTION 905.3 | | | C) AUTOMATIC CLOTHES WASHER STAND PIPE IS NOT | | | REQUIRED TO HAVE AN AIR HAMMER DEVISE IN THE DRAINAGE | | | SYSTEM PLEASE REMOVE. | | | D)AIR ADMITTANCE VALVE IS NOT REQUIRED IF THE | | | WASTE ARE IS LESS THAN 6 FEET. SHOW ON PLANS. FBC | | | PLUMBING 906.1 | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|