Plan Review Notes
Plan Review Notes For Permit 07070044
Permit Number 07070044
Review Stop P
Sequence Number 2
Notes
Date Text
2007-10-20 09:46:02DENIED;
 1. PAGE M-3 COLD WATER MAKE-UP DETAIL; 1" COLD WATER
 JUMPER AROUND BACKFLOW PREVENTER NOT PERMITED. CHECK
 VALVES CAN NOT BE TESTED AND MAY FAIL (INSTALLED ON
 BY-PASS). SUBMIT MANUFACTURE AND MOTEL NUMBER OF
 BACKFLOW.
 2. SANITARY RISER DIAGRAM; ( MARKED ON ONE SET OF
 PLANS.
 A) 2 KITCHEN SINKS SHOWN ON RISER DIAGRAM ONLY
 ONE ON PLANS, PLEASE CORRECT.
 B) HORIZONTALDRY VENTS NOT PERMITED SEE FBC
 PLUMBING SECTION 905.3
 C) AUTOMATIC CLOTHES WASHER STAND PIPE IS NOT
 REQUIRED TO HAVE AN AIR HAMMER DEVISE IN THE DRAINAGE
 SYSTEM PLEASE REMOVE.
 D)AIR ADMITTANCE VALVE IS NOT REQUIRED IF THE
 WASTE ARE IS LESS THAN 6 FEET. SHOW ON PLANS. FBC
 PLUMBING 906.1
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695