| 2007-10-18 10:41:08 | REVIEW #: 2 |
| | ACTION: DENIED |
| | |
| | FBC 2004 CODE FAMILY W/ 2005 AND 2006 SUPPLEMENTS |
| | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH |
| | |
| | THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH |
| | PREVIOUS REVIEW COMMENTS AS WELL AS DESIGNER'S WRITTEN |
| | RESPONSES FOR THE PURPOSE OF CONTINUITY. |
| | |
| | 1. ENERGY CODE: THIS BUILDING IS A RESIDENTIAL BUILDING |
| | GREATER THAN 3 STORIES, THEREFORE IT IS SUBJECT TO FBC |
| | SUBCHAPTER 13-4, NOT 13-6. ALSO, METHOD A COMPLIANCE IS |
| | NOT AVAILABLE FOR THIS JOB AS IT IS NOT A WHOLE |
| | BUILDING. SEE FBC 13-400.0.C.4. THIS DOES NOT MEET THE |
| | DEFINITION OF A RENOVATION UNDER FBC 13-202. |
| | |
| | COMMENTS 2 THROUGH 5: OK |
| | |
| | 6. THE KITCHEN EXHAUST IS NOT AN EXISTING CONDITION AND |
| | AS SUCH SHALL COMPLY WITH FBC,M 601.3. DUCT MAY BE |
| | ISOLATED FROM PLENUM AREAS OR THE FAN MAY BE LOCATED AT |
| | THE LOUVER TO ELIMINATE POSITIVE PRESSURE DUCT. |
| | |
| | 7 THROUGH 9: OK |
| | |
| | 10. OK, EXCEPT HOOD MANUFACTURER'S INSTRUCTIONS SHALL |
| | BE ON SITE AT TIME OF INSPECTION IN ACCORDANCE WITH |
| | FBC,M 304.1. |
| | |
| | 11. WHETHER THE WORK IS IN ANOTHER CONDO OR A COMMON |
| | AREA, IT IS STILL OUTSIDE THE PROPERTY OF UNIT 1903, |
| | WHICH IS THE BOUNDARY OF THE SCOPE OF THIS PERMIT. ANY |
| | WORK PERFORMED OUTSIDE OF THIS BOUNDARY MAY NOT BE |
| | PERFORMED UNDER THE SCOPE OF THIS PERMIT. THE NAME AND |
| | ADDRESS OF THE OWNER OF THE REAL PROPERTY, AS WELL AS A |
| | LEGAL DESCRIPTION OF THE REAL PROPERTY WHERE THE WORK |
| | IS TO TAKE PLACE SHALL BE CONTAINED ON ALL PERMIT |
| | APPLICATIONS IN ACCORDANCE WITH F.S. 713.135(5) |
| | |